| 2020-04-03 15:05:53 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT- 20030563 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | 1) PLEASE SHOW HOW YOU ARE MEETING CHAPTER 4 OF THE FBC |
| | M, ARE YOU USING NATURAL VENTILATION OR MECHANICAL? |
| | 2) PLEASE PROVIDE VENTILATION CALCULATIONS TO SHOW YOU |
| | ARE BRINGING THE MINIMUM REQUIRED OA INTO EACH AREA OF |
| | THE APARTMENTS. FBC M 403.3.2 |
| | 3) PLEASE PROVIDE INFORMATION FOR EACH AHU/CU. |
| | INCLUDING MAX. AIR SUPPLIED, RETURN AIR VOLUME AND OA |
| | NEEDED. . FBC WPB 107.2.1 |
| | 4) PLEASE SHOW HOW YOU ARE PROVIDING EXHAUST FROM THE |
| | KITCHENS. FBC M TABLE 430.3.1.1 |
| | 5) SHEET M.4.1- PLEASE SHOW ROOF ACCESS ON THIS SHEET |
| | OR GIVE A SHEET REFERENCE ON THIS SHEET SHOWING THE |
| | ROOF ACCESS. FBC M 306.5 |
| | 6) PLEASE PROVIDE A DRAWING SHOWING THE LOCATION OF THE |
| | DRYER. FBC WPB 107.2.1 |
| | 7) PLEASE PROVIDE DRYER DUCT LENGTHS FOR EACH UNIT. FBC |
| | M 504.8.4.1 |
| | 8) PLEASE SHOW DRYER DUCT MAKEUP AIR LOCATION AND SIZE |
| | OF DUCT OR TRANSFER GRILL. FBC M 504.6 |
| | 9) IF DRYER IS IN THE SAME CLOSET AS THE AHU SHOW HOW |
| | THIS DESIGN MEETS FBC M 602 FOR PLENUMS. |
| | 10) PLEASE PROVIDE CFM?S FOR ALL TRANSFER GRILLS AND |
| | RETURNS. FBC M 601.5 NOTES (3)&(4). |
| | 11) PLEASE PROVIDE A DETAILED DRAWING SHOWING THE MAKE |
| | UP OF THE RAG FROM MASTER BEDROOM TO LIVING. FBC WPB |
| | 107.2.1 |
| | 12) WHEN YOU DOWNLOADED THE SHEETS INTO PROJECTDOX YOU |
| | MISLABELED SHEET M5.2. THIS SHEET SHOULD REFERENCE UNIT |
| | 1B AND 2B. IN PROJECTDOX THE PAGE IS SHOWING 1B & 2A. |
| | 13) SHEET M-5.1 UNIT 1A PLEASE IDENTIFY THE AHU UNIT. |
| | FBC WPB 107.2.1 |
| | 14) SHEET M-5.1: UNIT 1A THE EXHAUST LOUVER THAT IS |
| | LABELED DRYER VENT LOUVER IS GOING TO EF-1 IN THE |
| | BATHROOM OFF FROM THE KITCHEN. PLEASE CORRECT THIS. FBC |
| | WPB 107.2.1 |
| | 15) SHEET M-5.1: UNIT 1A THE OTHER EXHAUST DUCT IS |
| | GOING TO A LOCATION IN THE CLOSET WITH THE DOUBLE DOORS |
| | AND APPEARS TO STOP. PLEASE PROVIDE A DETAIL DRAWING OF |
| | WHERE THIS DUCT TERMINATES. FBC WPB 107.2.1 |
| | 16) SHEET M-5.1: UNIT 1A PLEASE PROVIDE CFM?S FOR THE |
| | RETURN. FBC WPB 107.2.1 |
| | 17) SHEET M-5.1: PLEASE SHOW THAT ALL EXHAUST |
| | TERMINATIONS FOR THIS PROJECT MEET FBC M 501.3.1. |
| | 18) SHEET M-5.1: PLEASE SHOW THAT ALL O.A. INTAKES FOR |
| | THIS PROJECT MEET FBC M 401.4. |
| | 19) SHEET M-5.1: UNIT 2A IT APPEARS THAT THE DUCT |
| | LABELED ?DRYER VENT? IS GOING INTO THE AHU/WATER HEATER |
| | ROOM. DETAILS ON M6.1 DOES NOT SHOW A DRYER IN THIS |
| | LOCATION. |
| | 20) SHEET M-7.1: THERE ARE SEVERAL LOCATIONS ON THE |
| | SHEET THAT ARE NOT INCLUDED IN THIS PROJECT. PLEASE |
| | REMOVE ROOMS AND EQUIPMENT FROM THIS SHEET THAT ARE NOT |
| | RELATED TO THIS PERMITTED PROJECT. |
| | 21) SHEET M-5.2 SHOWS A UNIT 1B ON THE FIRST FLOOR. |
| | SHEET M-7.1 DOES NOT MENTION A 1B1 IN THE LOCATIONS |
| | COLUMN. PLEASE CORRECT THIS. . FBC WPB 107.2.1 |
| | 22) PLEASE VERIFY ACTUAL AIR FLOW FROM SHEET M-7.1 |
| | MATCHES THE INDIVIDUAL UNIT SHEETS. . FBC WPB 107.2. |
| | 23) SHEET M-6.2 PLEASE SHOW THAT THE MINI-SPLIT UNITS |
| | MEET SECTION 307.2.4.1 OF FBC M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |