| 2020-03-27 16:25:17 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET FA 2.1 - THERE DOES NOT APPEAR TO BE |
| | NOTIFICATION DEVICES WITHIN THE SLEEPING ROOMS |
| | |
| | PER NFPA 101, CH 30 |
| | |
| | 30.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS. |
| | 30.3.4.1 GENERAL. |
| | 30.3.4.1.1 APARTMENT BUILDINGS FOUR OR MORE STORIES IN |
| | HEIGHT OR |
| | WITH MORE THAN 11 DWELLING UNITS, OTHER THAN THOSE |
| | MEETING THE |
| | REQUIREMENTS OF 30.3.4.1.2, SHALL BE PROVIDED WITH A |
| | FIRE ALARM |
| | SYSTEM IN ACCORDANCE WITH SECTION 9.6, EXCEPT AS |
| | MODIFIED BY |
| | 30.3.4.2 THROUGH 30.3.4.5. |
| | |
| | 30.3.4.3 NOTIFICATION. |
| | 30.3.4.3.1 OCCUPANT NOTIFICATION SHALL BE PROVIDED |
| | AUTOMATICALLY |
| | IN ACCORDANCE WITH SECTION 9.6, AND BOTH OF THE |
| | FOLLOWING SHALL |
| | ALSO APPLY: |
| | (1) VISIBLE SIGNALS SHALL BE INSTALLED IN UNITS |
| | DESIGNED FOR THE |
| | HEARING IMPAIRED. |
| | (2) POSITIVE ALARM SEQUENCE IN ACCORDANCE WITH 9.6.3.4 |
| | SHALL BE |
| | PERMITTED. |
| | |
| | 9.6.3.5 UNLESS OTHERWISE PROVIDED IN 9.6.3.5.1 THROUGH |
| | 9.6.3.5.8, |
| | NOTIFICATION SIGNALS FOR OCCUPANTS TO EVACUATE SHALL BE |
| | AUDIBLE, AND |
| | VISIBLE SIGNALS IN ACCORDANCE WITH NFPA 72, NATIONAL |
| | FIRE ALARM |
| | AND SIGNALING CODE. AND ICC/ANSI A117.1, AMERICAN |
| | NATIONAL |
| | STANDARD FOR ACCESSIBLE AND USABLE BUILDINGS AND |
| | FACILITIES, OR |
| | OTHER MEANS OF NOTIFICATION ACCEPTABLE TO THE AUTHORITY |
| | HAVING |
| | JURISDICTION SHALL BE PROVIDED. |
| | |
| | NFPA 72 |
| | |
| | 18.4.5 SLEEPING AREA REQUIREMENTS. |
| | 18.4.5.1* WHERE AUDIBLE APPLIANCES ARE INSTALLED TO |
| | PROVIDE |
| | SIGNALS FOR SLEEPING AREAS, THEY SHALL HAVE A SOUND |
| | LEVEL OF AT |
| | LEAST 15 DB ABOVE THE AVERAGE AMBIENT SOUND LEVEL OR 5 |
| | DB |
| | ABOVE THE MAXIMUM SOUND LEVEL HAVING A DURATION OF AT |
| | LEAST |
| | 60 SECONDS OR A SOUND LEVEL OF AT LEAST 75 DBA, |
| | WHICHEVER IS |
| | GREATER, MEASURED AT THE PILLOW LEVEL IN THE AREA |
| | REQUIRED TO BE |
| | SERVED BY THE SYSTEM USING THE A-WEIGHTED SCALE (DBA). |
| | 18.4.5.2 IF ANY BARRIER, SUCH AS A DOOR, CURTAIN, OR |
| | RETRACTABLE |
| | PARTITION, IS LOCATED BETWEEN THE NOTIFICATION |
| | APPLIANCE AND |
| | THE PILLOW, THE SOUND PRESSURE LEVEL SHALL BE MEASURED |
| | WITH THE |
| | BARRIER PLACED BETWEEN THE APPLIANCE AND THE PILLOW. |
| | |
| | PLEASE REVIEW AND CORRECT OR PROVIDE SPECIFIC CODE |
| | REFERENCES AND NARRATIVE AS TO WHY NOT. |
| | |
| | |
| | |
| | 1A) FOR INFORMATIONAL AND FALSE ALARM REDUCTION |
| | PURPOSES THE LOCATION OF MAUNAL PULL STATIONS MAY BE |
| | REDUCED PER NFPA 101, CH 9 |
| | |
| | 9.6.2.6* FOR FIRE ALARM SYSTEMS USING AUTOMATIC FIRE |
| | DETECTION OR |
| | WATERFLOW DETECTION DEVICES TO INITIATE THE FIRE ALARM |
| | SYSTEM IN |
| | ACCORDANCE WITH CHAPTERS 11 THROUGH 43, NOT LESS THAN |
| | ONE MANUAL |
| | FIRE ALARM BOX, LOCATED AS REQUIRED BY THE AUTHORITY |
| | HAVING |
| | JURISDICTION, SHALL BE PROVIDED TO INITIATE A FIRE |
| | ALARM SIGNAL. |
| | |
| | A.9.6.2.6 THE MANUAL FIRE ALARM BOX REQUIRED BY 9.6.2.6 |
| | IS INTENDED |
| | TO PROVIDE A MEANS TO MANUALLY ACTIVATE THE FIRE ALARM |
| | SYSTEM WHEN THE AUTOMATIC FIRE DETECTION SYSTEM OR |
| | WATERFLOW DEVICES |
| | ARE OUT OF SERVICE DUE TO MAINTENANCE OR TESTING, OR |
| | WHERE |
| | HUMAN DISCOVERY OF THE FIRE PRECEDES AUTOMATIC |
| | SPRINKLER SYSTEM |
| | OR AUTOMATIC DETECTION SYSTEM ACTIVATION. WHERE THE |
| | FIRE ALARM |
| | SYSTEM IS CONNECTED TO A MONITORING FACILITY, THE |
| | MANUAL FIRE |
| | ALARM BOX REQUIRED BY 9.6.2.6 SHOULD BE CONNECTED TO A |
| | SEPARATE |
| | CIRCUIT THAT IS NOT PLACED ?ON TEST? WHEN THE DETECTION |
| | OR SPRINKLER |
| | SYSTEM IS PLACED ON TEST. THE MANUAL FIRE ALARM BOX |
| | SHOULD BE |
| | LOCATED IN AN AREA THAT IS ACCESSIBLE TO OCCUPANTS OF |
| | THE BUILDING |
| | AND SHOULD NOT BE LOCKED. |
| | |
| | PLEASE REVIEW AND IF IN AGREEMENT, CONSULT WITH MY |
| | OFFICE FOR A SUITABLE LOCATION |
| | |
| | PROVIDE AN APPLICABLE NOTE. |
| | |
| | |
| | 2) SHEET FP 2 - NO FIRE SPRINKLER IN THE ELEVATOR PIT |
| | |
| | PER NFPA 13R |
| | |
| | 6.6.8 ALL SITUATIONS REGARDING SPRINKLER LOCATION AND |
| | POSITION |
| | THAT ARE NOT DIRECTLY DISCUSSED IN NFPA 13R SHALL BE IN |
| | ACCORDANCE |
| | WITH NFPA 13. |
| | |
| | 8.15.5 ELEVATOR HOISTWAYS AND MACHINE ROOMS. |
| | 8.15.5.1* SIDEWALL SPRAY SPRINKLERS SHALL BE INSTALLED |
| | AT THE BOTTOM |
| | OF EACH ELEVATOR HOISTWAY NOT MORE THAN 2 FT (0.61 M) |
| | ABOVE THE FLOOR OF THE PIT. |
| | 8.15.5.2 THE SPRINKLER REQUIRED AT THE BOTTOM OF THE |
| | ELEVATOR |
| | HOISTWAY BY 8.15.5.1 SHALL NOT BE REQUIRED FOR |
| | ENCLOSED, NONCOMBUSTIBLE |
| | ELEVATOR SHAFTS THAT DO NOT CONTAIN COMBUSTIBLE |
| | HYDRAULIC FLUIDS. |
| | 8.15.5.3 AUTOMATIC FIRE SPRINKLERS SHALL NOT BE |
| | REQUIRED IN ELEVATOR |
| | MACHINE ROOMS, ELEVATOR MACHINERY SPACES, CONTROL |
| | SPACES, OR |
| | HOISTWAYS OF TRACTION ELEVATORS INSTALLED IN ACCORDANCE |
| | WITH THE |
| | APPLICABLE PROVISIONS IN NFPA 101, OR THE APPLICABLE |
| | BUILDING |
| | CODE, WHERE ALL OF THE FOLLOWING CONDITIONS ARE MET: |
| | (1) THE ELEVATOR MACHINE ROOM, MACHINERY SPACE, CONTROL |
| | ROOM, CONTROL SPACE, OR HOISTWAY OF TRACTION ELEVATOR |
| | IS |
| | DEDICATED TO ELEVATOR EQUIPMENT ONLY. |
| | (2) THE ELEVATOR MACHINE ROOM, MACHINE ROOM, MACHINERY |
| | SPACE, CONTROL ROOM, CONTROL SPACE, OR HOISTWAY OF |
| | TRACTION |
| | ELEVATORS ARE PROTECTED BY SMOKE DETECTORS, OR OTHER |
| | AUTOMATIC |
| | FIRE DETECTION, INSTALLED IN ACCORDANCE WITH NFPA72. |
| | (3) THE ELEVATOR MACHINERY SPACE, CONTROL ROOM, CONTROL |
| | SPACE, |
| | OR HOISTWAY OF TRACTION ELEVATORS IS SEPARATED FROM THE |
| | REMAINDER |
| | OF THE BUILDING BY WALLS AND FLOOR/CEILING OR ROOF/ |
| | CEILING ASSEMBLIES HAVING A FIRE RESISTANCE RATING OF |
| | NOT LESS |
| | THAN THAT SPECIFIED BY THE APPLICABLE BUILDING CODE. |
| | (4) NO MATERIALS UNRELATED TO ELEVATOR EQUIPMENT ARE |
| | PERMITTED |
| | TO BE STORED IN ELEVATOR MACHINE ROOMS, MACHINERY |
| | SPACES, CONTROL ROOMS, CONTROL SPACES, OR HOISTWAYS OF |
| | TRACTION |
| | ELEVATORS. |
| | (5) THE ELEVATOR MACHINERY IS NOT OF THE HYDRAULIC |
| | TYPE. |
| | 8.15.5.4* AUTOMATIC SPRINKLERS IN ELEVATOR MACHINE |
| | ROOMS OR |
| | AT THE TOPS OF HOISTWAYS SHALL BE OF ORDINARY- OR |
| | INTERMEDIATETEMPERATURE |
| | RATING. |
| | 8.15.5.5* UPRIGHT, PENDENT, OR SIDEWALL SPRAY |
| | SPRINKLERS SHALL |
| | BE INSTALLED AT THE TOP OF ELEVATOR HOISTWAYS. |
| | 8.15.5.6 THE SPRINKLER REQUIRED AT THE TOP OF THE |
| | ELEVATOR HOISTWAY |
| | BY 8.15.5.5 SHALL NOT BE REQUIRED WHERE THE HOISTWAY |
| | FOR PASSENGER |
| | ELEVATORS IS NONCOMBUSTIBLE OR LIMITED-COMBUSTIBLE AND |
| | THE CAR ENCLOSURE MATERIALS MEET THE REQUIREMENTS OF |
| | ASME |
| | A17.1, SAFETY CODE FOR ELEVATORS AND ESCALATORS. |
| | |
| | 8.15.5.7 COMBUSTIBLE SUSPENSION IN ELEVATORS. |
| | 8.15.5.7.1 SPRINKLERS SHALL BE INSTALLED AT THE TOP AND |
| | BOTTOM OF |
| | ELEVATOR HOISTWAYS WHERE ELEVATORS UTILIZE COMBUSTIBLE |
| | SUSPENSION |
| | MEANS SUCH AS NONCIRCULAR ELASTOMERIC-COATED OR |
| | POLYURETHANECOATED |
| | STEEL BELTS. |
| | 8.15.5.7.2 THE SPRINKLERS IN THE ELEVATOR HOISTWAY |
| | SHALL NOT BE |
| | REQUIRED WHEN THE SUSPENSION MEANS PROVIDE NOT LESS |
| | THAN AN |
| | FT-1 RATING WHEN TESTED TO THE VERTICAL BURN TEST |
| | REQUIREMENTS |
| | OF UL 62, FLEXIBLE CORDS AND CABLES, AND UL 1581, |
| | REFERENCE STANDARD |
| | FOR ELECTRICAL WIRES, CABLES, AND FLEXIBLE CORDS. |
| | |
| | PLEASE REVIEW AND PROVIDE DETAILS OR CORRECT |
| | |
| | |
| | |
| | 3) SHEET 2.3 - THERE ARE INDICATIONS OF FIRE LINE |
| | UNDERGROUND. |
| | |
| | ALL FIRE LAINE UNDERGROUND WORK SHALL BE DONE UNDER |
| | SEPARATE PERMIT AND SHOP DRAWINGS IN COMPLIANCE WITH |
| | NFPA 24, STANDARD FOR THE |
| | INSTALLATION OF PRIVATE FIRE SERVICE MAINS AND THEIR |
| | APPURTENANCES,2013 EDITION |
| | |
| | PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF |
| | ACKNOWLEDGEMENT. |
| | |
| | |
| | |
| | 4) SHEET E 7.4 - THERE ARE INDICATIONS OF A BDA SYSTEM. |
| | |
| | NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY |
| | RADIO ENHANCEMENT SERVICES. |
| | 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM |
| | RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT |
| | COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL |
| | DETERMINED BY THE AHJ. |
| | NFPA 72, 24.5.2* TWO-WAY RADIO COMMUNICATIONS |
| | ENHANCEMENT SYSTEMS. |
| | 24.5.2.2 RADIO COVERAGE. RADIO COVERAGE SHALL BE |
| | PROVIDED THROUGHOUT THE BUILDING AS A PERCENTAGE OF |
| | FLOOR AREA AS SPECIFIED IN 24.5.2.2.1 THROUGH |
| | 24.5.2.2.3. |
| | 24.5.2.2.1 CRITICAL AREAS. CRITICAL AREAS, SUCH AS THE |
| | EMERGENCY COMMAND CENTER(S), THE FIRE PUMP ROOM(S), |
| | EXIT STAIRS, EXIT PASSAGEWAYS, ELEVATOR LOBBIES, |
| | STANDPIPE CABINETS, SPRINKLER SECTIONAL VALVE |
| | LOCATIONS, AND OTHER AREAS DEEMED CRITICAL BY THE |
| | AUTHORITY HAVING JURISDICTION, SHALL BE PROVIDED WITH |
| | 99 PERCENT FLOOR AREA RADIO COVERAGE. |
| | 24.5.2.2.2 GENERAL BUILDING AREAS. GENERAL BUILDING |
| | AREAS SHALL BE PROVIDED WITH 90 PERCENT FLOOR AREA |
| | RADIO COVERAGE. |
| | 24.5.2.3 SIGNAL STRENGTH. |
| | 24.5.2.3.1 INBOUND. A MINIMUM INBOUND SIGNAL STRENGTH |
| | OF -95 DBM, OR OTHER SIGNAL STRENGTH AS REQUIRED BY THE |
| | AUTHORITY HAVING JURISDICTION, SHALL BE PROVIDED |
| | THROUGHOUT THE COVERAGE AREA. |
| | 24.5.2.3.2 OUTBOUND. A MINIMUM OUTBOUND SIGNAL STRENGTH |
| | OF -95 DBM AT THE DONOR SITE, OR OTHER SIGNAL STRENGTH |
| | AS REQUIRED BY THE AUTHORITY HAVING JURISDICTION, SHALL |
| | BE PROVIDED FROM THE COVERAGE AREA. |
| | |
| | THE SYSTEM SHALL MAINTAIN A MINIMUM RADIO SIGNAL |
| | STRENGTH OF -95 DBM FOR THE RADIO SYSTEM USED BY WEST |
| | PALM BEACH FIRE RESCUE. TESTING SHALL BE BY AN |
| | ACCEPTABLE NATIONAL STANDARD DOCUMENTING PERCENTAGES |
| | NOTED ABOVE AND BY ACTUAL RADIO TESTING BY FIRE |
| | PERSONNEL. IF THE MINIMUM CANNOT BE MAINTAINED, A |
| | BI-DIRECTIONAL AMPLIFIED SYSTEM SHALL BE INSTALLED WITH |
| | A MINIMUM 2-HOUR RUN TIME BATTERY BACK-UP. |
| | |
| | |
| | YOU SHALL MAKE CONTACT AND COORDINATE WITH MARK FILLA, |
| | PALM BEACH COUNTY, PUBLIC SAFETY RADIO SYSTEMS MANAGER, |
| | FOR ALL RADIO SIGNAL DETAILS, OUTBOUND SIGNAL STRENGTH |
| | AND ANTENNA DIRECTION, AS OUR RADIOS OPERATE ON THAT |
| | SYSTEM. |
| | [email protected] 561-233-0837 |
| | |
| | |
| | ALL BDA WORK SHALL BE INSTALLED UNDER SEPARATE PERMIT |
| | AND SHOP DRAWINGS BY A QUALIFIED FCC LIC CONTRACTOR, |
| | LISTED EQUIPMENT AND SPEC SHEETS, WITH A COLOR HEAT |
| | SPECTUM FLOOR PLAN. |
| | |
| | PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF |
| | ACKNOWLEDGEMENT. |
| | |
| | |
| | |
| | 5) SHEET G 1.2 - THERE ARE INDICATIONS OF A GAZEBO WITH |
| | A BBQ INSTALLED; HOWEVER, THERE IS NO INDICATION OF |
| | WHAT TYPE OF GRILL AND IF IT IS OF PERMANENT MOUNTING |
| | PER MANUFACTURES SPEC. |
| | |
| | PLEAE PROVIDE THE TYPE AND MANAFCATURES SPECS. |
| | |
| | |
| | 5A) SHEET G 1.2 - THERE IS NO INDICATION OF A FIRE |
| | EXTINGUISHER AT THE GAZEBO AREA. |
| | |
| | PLEASE PROIVDE AT LEAT A 5LB ABC FIRE EXTINGUISHER IN |
| | THIS AREA THAT IS CERTIFIED AND TAG BY A THRID PARTY FE |
| | COMPANY. |
| | |
| | |
| | |
| | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |