Plan Review Notes
Plan Review Notes For Permit 20030563
Permit Number 20030563
Review Stop E
Sequence Number 1
Notes
Date Text
2020-04-21 14:32:06CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. FIRE ALARM, LOW VOLTAGE SYSTEMS, DAS, LIGHTNING
 PROTECTION, GENERATORS, COMMERCIAL HOOD SYSTEMS, WALK
 IN COOLERS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND PLAN SUBMITTALS FOR ANY
 OF THESE SYSTEMS PRESENT. WPB FBC 105.1, 107.2.1
 2. RISER DIAGRAM SHOWS THREE SETS OF THREE 400 KCMIL
 CONDUCTORS FOR THE FEEDERS FROM FPL. THIS WOULD
 INDICATE THAT THIS IS A SINGLE PHASE SERVICE, BUT THE
 RISER INDICATED THIS IS A THREE PHASE SERVICE. PROVIDE
 CLARIFICATION AND/OR CORRECTIONS. NEC 215.5; WPB FBC
 107.2.1
 3. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. IT APPEARS FOR THE METER CENTER THAT NEC 220.84
 IS BEING USED, BUT THIS CODE SECTION IS NOT APPLIED
 CORRECTLY. ALL LOADS AT 100% SHOULD BE ADDED TOGETHER
 AND THEN THE DEMAND FACTOR OF 34% APPLIED TO THIS
 AMOUNT BASED ON 26 DWELLING UNITS. IT ALSO APPEARS THAT
 100% OF THE LOADS FROM EACH UNIT IS NOT BEING USED
 CORRECTLY. THIS SHOULD INCLUDE ALL ITEMS DETAILED IN
 NEC 220.84(C), INCLUDING ONLY THE LARGER OF THE AC OR
 HEAT LOAD. WHEN THIS NUMBER IS CALCULATED, THEN 100% OF
 THE HOUSE LOAD WOULD BE ADDED TO THAT FOR THE FINAL VA
 LOAD BASED ON NEC 220.84(B). NEC 220
 4. BASED ON LOADS DETAILED IN THIS SUBMISSION, I HAVE
 CALCULATED THE LOAD ON THE SERVICE TO BE 1078 AMPS,
 WHICH IS LARGER THAN THE DESIGNED SERVICE SUPPLIED.
 PROVIDE CLARIFICATIONS AND/OR CORRECTIONS AS NEEDED FOR
 SERVICE EQUIPMENT AND FEEDERS. NEC 215.2, 220.84,
 408.30, 408.36
 5. PANEL SCHEDULE FOR EACH UNIT SHOW A DIFFERENT LOAD
 THAN THE LOAD CALCULATION TABLES. IT APPEARS THAT THIS
 IS DUE TO THE CORRECT TYPE OF LOAD CALCULATION FOR
 DWELLING UNITS NOT BEING USED, WHICH WOULD INCLUDE 3VA
 PER SQUARE FOOT. INFORMATION SHOULD BE CONSISTENT.
 CORRECT DISCREPANCIES. WPB FBC 107.2.1; NEC 220
 6. IF SERVICE OR FEEDER SIZES ARE CHANGED, PROVIDE
 UPDATED AIC CALCULATIONS. NEC 110.9, 110.10
 7. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 8. UNITS 2A AND 2B ALL SHOW THE FOLLOWING CODE
 VIOLATION. A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT
 SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE
 OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS.
 THIS CIRCUIT CAN BE USED FOR LIGHTING AND RECEPTACLE
 OUTLETS IN ONE BATHROOM, BUT THEN CANNOT BE USED TO
 FEED ANOTHER BATHROOM. OR, THIS CIRCUIT CAN FEED ONLY
 THE RECEPTACLES IN MULTIPLE BATHROOMS. PROVIDE
 CORRECTION. NEC 210.11(C)(3)
 9. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12
 10. LIGHT FIXTURE SCHEDULE DOES NOT INDICATE FIXTURES
 THAT ARE RATED FOR WET LOCATIONS FOR SHOWERS, OR HAVE
 ENCLOSED LIGHT BULBS FOR CLOSETS. PROVIDE NOTE OF
 COMPLIANCE FOR EACH LOCATION. NEC 410.10(D), 410.16
 11. PROVIDE COMPLIANCE FOR DWELLING UNITS: A MINIMUM OF
 75 PERCENT OF THE LAMPS IN PERMANENTLY INSTALLED
 LIGHTING FIXTURES SHALL BE HIGH-EFFICACY LAMPS OR A
 MINIMUM OF 75 PERCENT OF THE PERMANENTLY INSTALLED
 LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH EFFICACY
 LAMPS. A NOTE WILL SUFFICE. FBC EC C405.1, R404.1
 12. AFCI PROTECTION SHOWN IS NOT CODE COMPLIANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12
 13. THERE IS A DISCREPANCY WITH FLOOR PLAN, RISER
 DIAGRAM AND LOAD CALCULATIONS. THE RISER SHOWS A UNIT
 1209, BUT THIS IS NOT INCLUDED IN LOAD CALCS OR FLOOR
 PLAN. IT APPEARS THAT THE HOUSE PANEL HAS BEEN CONFUSED
 FOR UNIT 1205. CORRECT DISCREPANCIES SO THAT ALL
 INFORMATION IS CONSISTENT. WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  