2020-04-29 11:31:50CARPORT ENCLOSURE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED -
 THE ENCLOSURE FRAMING CANNOT BE BUILT USING CODE
 PERSCRIPTIVE FRAMING AND CONNECTIONS - YOU WILL NEED TO
 PROVIDE THE WIND DESIGN CALCULATIONS FOR THE ENCLOSURE
 USING WIND SPEEDS 170MPH, EXPOSURE "B" "C" OR "D" AS
 APPLICABLE.
 1) PLEASE SHOW THE WIND LOAD CALCULATIONS TO COMPLY
 WITH THE WIND LOADS OR HAVE THE DRAWINGS SIGNED AND
 SEALED BY AN ARCHITECT OR ENGINEER. FBC 1609
 FBC R301.2.1.1 WIND LIMITATIONS AND WIND DESIGN
 REQUIRED.
 THE PRESCRIPTIVE PROVISIONS OF THIS CODE FOR WOOD
 CONSTRUCTION, COLD-FORMED STEEL LIGHT-FRAME
 CONSTRUCTION, AND MASONRY CONSTRUCTION SHALL NOT APPLY
 TO THE DESIGN OF BUILDINGS WHERE THE ULTIMATE DESIGN
 WIND SPEED, VULT, FROM FIGURE R301.2(4) EQUALS OR
 EXCEEDS 115 MILES PER HOUR (51 M/S).
 FBC 1609.1.1DETERMINATION OF WIND LOADS.
 WIND LOADS ON EVERY BUILDING OR STRUCTURE SHALL BE
 DETERMINED IN ACCORDANCE WITH CHAPTERS 26 TO 30 OF ASCE
 7 OR PROVISIONS OF THE ALTERNATE ALL-HEIGHTS METHOD IN
 SECTION 1609.6
 PLEASE SHOW THE COMPLETE CALCULATIONS FOR THE WIND
 DESIGN FOR THE ENCLOSURE.
 2) WIND DESIGN PRESSURE ENGINEERING PROVIDED FOR THE
 WINDOW OPENINGS NEEDS HAVE A DIGITAL SIGNATURE PROVIDED
 BY THE ARCHITECT OR ENGINEER TO BE USED IN ELECTRONIC
 PLAN REVIEW. PLEASE CONTACT THE ENGINEER OR ARCHITECT
 AND ASK FOR THE ENGINEERING TO BE DIGITALLY SIGNED. A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF E-SIGNATURE.
 WHEN PROVIDED IT CANNOT BE PRINTED OUT IT WILL LOSE THE
 DIGITAL SIGNATURE ? IT MUST TRAVEL IN THE COMPUTER.