| 2020-04-14 15:39:39 | CARPORT ENCLOSURE | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | | | | CORRECTIONS NEEDED - | | | 1) PLEASE SHOW THE WIND LOAD CALCULATIONS TO COMPLY | | | WITH THE WIND LOADS OR HAVE THE DRAWINGS SIGNED AND | | | SEALED BY AN ARCHITECT OR ENGINEER. FBC 1609 | | | FBC R301.2.1.1WIND LIMITATIONS AND WIND DESIGN | | | REQUIRED. | | | THE PRESCRIPTIVE PROVISIONS OF THIS CODE FOR WOOD | | | CONSTRUCTION, COLD-FORMED STEEL LIGHT-FRAME | | | CONSTRUCTION, AND MASONRY CONSTRUCTION SHALL NOT APPLY | | | TO THE DESIGN OF BUILDINGS WHERE THE ULTIMATE DESIGN | | | WIND SPEED, VULT, FROM FIGURE R301.2(4) EQUALS OR | | | EXCEEDS 115 MILES PER HOUR (51 M/S). | | | FBC 1609.1.1DETERMINATION OF WIND LOADS. | | | WIND LOADS ON EVERY BUILDING OR STRUCTURE SHALL BE | | | DETERMINED IN ACCORDANCE WITH CHAPTERS 26 TO 30 OF ASCE | | | 7 OR PROVISIONS OF THE ALTERNATE ALL-HEIGHTS METHOD IN | | | SECTION 1609.6 | | | PLEASE SHOW THE COMPLETE CALCULATIONS. | | | |
|