| 2020-03-17 13:49:02 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT 20030557 |
| | |
| | CODES IN EFFECT: |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | R303.10 REQUIRED HEATING. |
| | DESIGN TEMP. WEST PALM BEACH FLORIDA ? 45 DEGREES - |
| | WINTER |
| | |
| | FBC RESIDENTIAL, CHAPTER 3 BUILDING PLANNING, SECTION |
| | R303.10 REQUIRED HEATING. WHERE THE WINTER DESIGN |
| | TEMPERATURE IN TABLE R301.2(1) IS BELOW 60?F (16?C), |
| | EVERY DWELLING UNIT SHALL BE PROVIDED WITH HEATING |
| | FACILITIES CAPABLE OF MAINTAINING A ROOM TEMPERATURE OF |
| | NOT LESS THAN 68?F (20?C) AT A POINT 3 FEET (914 MM) |
| | ABOVE THE FLOOR AND 2 FEET (610 MM) FROM EXTERIOR WALLS |
| | IN HABITABLE ROOMS AT THE DESIGN TEMPERATURE. THE |
| | INSTALLATION OF ONE OR MORE PORTABLE SPACE HEATERS |
| | SHALL NOT BE USED TO ACHIEVE COMPLIANCE WITH THIS |
| | SECTION. |
| | TABLE R301.2 (1), WINTER DESIGN TEMP. (E) ?THE OUTDOOR |
| | DESIGN DRY-BULB TEMPERATURE SHALL BE SELECTED FROM THE |
| | COLUMNS OF 971/2 PERCENT VALUES FOR WINTER??. |
| | 2017 FBC EXISTING BUILDING, CHPT. 11, ADDITIONS, |
| | SECTION 1101.1 SCOPE. ?AN ADDITION TO A BUILDING OR |
| | STRUCTURE SHALL COMPLY WITH THE FLORIDA BUILDING CODE |
| | AS ADOPTED FOR NEW CONSTRUCTION?? |
| | SECTION 1106 ENERGY CONSERVATION, 1106.1 MINIMUM |
| | REQUIREMENTS. ADDITIONS TO EXISTING BUILDINGS OR |
| | STRUCTURES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, ENERGY. |
| | |
| | 2017 FBC ENERGY, CHAPTER 5 (RE), EXISTING BUILDINGS, |
| | SECTION R502 ADDITIONS, ?ADDITIONS TO AN EXISTING |
| | BUILDING, BUILDING SYSTEM OR PORTION THEREOF SHALL |
| | CONFORM TO THE PROVISIONS OF THIS CODE AS THOSE |
| | PROVISIONS RELATE TO NEW CONSTRUCTION??. |
| | SECTION R502.1.1.2 HEATING AND COOLING SYSTEMS. NEW |
| | HEATING, COOLING AND DUCT SYSTEMS THAT ARE PART OF THE |
| | ADDITION SHALL COMPLY WITH SECTIONS RE403.1, RE403.2, |
| | RE403.3, R403.5 AND R403.6. |
| | FBC PLUMBING, APPENDIX D, DEGREE DAY AND DESIGN |
| | TEMPERATURES, TABLE D101, DESIGN TEMPERATURE, WINTER, |
| | 97 ?% = 45 DEGREES DESIGN TEMP. |
| | |