2020-03-17 13:49:021ST REVIEW FBC-2017 MECHANICAL
 PERMIT 20030557
  
 CODES IN EFFECT:
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 R303.10 REQUIRED HEATING.
 DESIGN TEMP. WEST PALM BEACH FLORIDA ? 45 DEGREES -
 WINTER
  
 FBC RESIDENTIAL, CHAPTER 3 BUILDING PLANNING, SECTION
 R303.10 REQUIRED HEATING. WHERE THE WINTER DESIGN
 TEMPERATURE IN TABLE R301.2(1) IS BELOW 60?F (16?C),
 EVERY DWELLING UNIT SHALL BE PROVIDED WITH HEATING
 FACILITIES CAPABLE OF MAINTAINING A ROOM TEMPERATURE OF
 NOT LESS THAN 68?F (20?C) AT A POINT 3 FEET (914 MM)
 ABOVE THE FLOOR AND 2 FEET (610 MM) FROM EXTERIOR WALLS
 IN HABITABLE ROOMS AT THE DESIGN TEMPERATURE. THE
 INSTALLATION OF ONE OR MORE PORTABLE SPACE HEATERS
 SHALL NOT BE USED TO ACHIEVE COMPLIANCE WITH THIS
 SECTION.
 TABLE R301.2 (1), WINTER DESIGN TEMP. (E) ?THE OUTDOOR
 DESIGN DRY-BULB TEMPERATURE SHALL BE SELECTED FROM THE
 COLUMNS OF 971/2 PERCENT VALUES FOR WINTER??.
 2017 FBC EXISTING BUILDING, CHPT. 11, ADDITIONS,
 SECTION 1101.1 SCOPE. ?AN ADDITION TO A BUILDING OR
 STRUCTURE SHALL COMPLY WITH THE FLORIDA BUILDING CODE
 AS ADOPTED FOR NEW CONSTRUCTION??
 SECTION 1106 ENERGY CONSERVATION, 1106.1 MINIMUM
 REQUIREMENTS. ADDITIONS TO EXISTING BUILDINGS OR
 STRUCTURES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, ENERGY.
  
 2017 FBC ENERGY, CHAPTER 5 (RE), EXISTING BUILDINGS,
 SECTION R502 ADDITIONS, ?ADDITIONS TO AN EXISTING
 BUILDING, BUILDING SYSTEM OR PORTION THEREOF SHALL
 CONFORM TO THE PROVISIONS OF THIS CODE AS THOSE
 PROVISIONS RELATE TO NEW CONSTRUCTION??.
 SECTION R502.1.1.2 HEATING AND COOLING SYSTEMS. NEW
 HEATING, COOLING AND DUCT SYSTEMS THAT ARE PART OF THE
 ADDITION SHALL COMPLY WITH SECTIONS RE403.1, RE403.2,
 RE403.3, R403.5 AND R403.6.
 FBC PLUMBING, APPENDIX D, DEGREE DAY AND DESIGN
 TEMPERATURES, TABLE D101, DESIGN TEMPERATURE, WINTER,
 97 ?% = 45 DEGREES DESIGN TEMP.
  