| Plan Review Notes For Permit 20030557 |
| Permit Number |
20030557 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-03-23 12:04:43 | CARPORT ENCLOSURE | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | | | | CORRECTIONS NEEDED - | | | 1) PLEASE SHOW THE WIND LOAD CALCULATIONS TO COMPLY | | | WITH THE WIND LOADS OR HAVE THE DRAWINGS SIGNED AND | | | SEALED BY AN ARCHITECT OR ENGINEER. FBC 1609 | | | 2) PLEASE SHOW THE WIND LOAD DESIGN CRITERIA USED FOR | | | DESIGN PER FBC 1609.3 | | | 3) THE PRODUCT APPROVAL SUPPLIED FOR THE SINGLE HUNG | | | WINDOWS IS APPROVED FOR SMALL MISSILE IMPACT - WINDOWS | | | BELOW 30 FEET FROM GRADE NEED TO COMPLY WITH LARGE | | | MISSILE IMPACT. PLEASE PROVIDE THE PRODUCT APPROVAL FOR | | | THE REQUIRED SHUTTERS. FBC R301.2.1.2 | | | 4) MEANS OF EGRESS TREAD DEPTH IS A MIN. OF 10 INCHES - | | | FBC R311.7.5.2 | | | 5) MEANS OF EGRESS MAX. RISER HEIGHT IS 7 3/4 INCHES - | | | FBC R311.7.5.1 | | | 6) PLEASE SHOW THE CEILING HEIGHT TO COMPLY WITH FBC | | | R305.1 |
|