2020-03-23 12:04:43CARPORT ENCLOSURE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED -
 1) PLEASE SHOW THE WIND LOAD CALCULATIONS TO COMPLY
 WITH THE WIND LOADS OR HAVE THE DRAWINGS SIGNED AND
 SEALED BY AN ARCHITECT OR ENGINEER. FBC 1609
 2) PLEASE SHOW THE WIND LOAD DESIGN CRITERIA USED FOR
 DESIGN PER FBC 1609.3
 3) THE PRODUCT APPROVAL SUPPLIED FOR THE SINGLE HUNG
 WINDOWS IS APPROVED FOR SMALL MISSILE IMPACT - WINDOWS
 BELOW 30 FEET FROM GRADE NEED TO COMPLY WITH LARGE
 MISSILE IMPACT. PLEASE PROVIDE THE PRODUCT APPROVAL FOR
 THE REQUIRED SHUTTERS. FBC R301.2.1.2
 4) MEANS OF EGRESS TREAD DEPTH IS A MIN. OF 10 INCHES -
 FBC R311.7.5.2
 5) MEANS OF EGRESS MAX. RISER HEIGHT IS 7 3/4 INCHES -
 FBC R311.7.5.1
 6) PLEASE SHOW THE CEILING HEIGHT TO COMPLY WITH FBC
 R305.1