Plan Review Notes
Plan Review Notes For Permit 20030483
Permit Number 20030483
Review Stop E
Sequence Number 1
Notes
Date Text
2020-03-27 10:51:55CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1) SHEET A1 OF THE PLANS INDICATES THAT THE EXISTING
 SERVICE IS TO BE MOVED. THE ELECTRICAL PLAN ON A4 SHOWS
 THE SERVICE ON THE NEW BEDROOM ADDITION AND HAS IT
 LABELED AS EXISTING. PLEASE CORRECT. PROVIDE RISER
 DIAGRAM, SHOWING ALL DETAILS OF SERVICE EQUIPMENT,
 UNDERGROUND OR OVERHEAD SERVICE, WIRE AND BREAKER SIZES
 FOR SERVICE AND FEED TO ANY SUB-PANEL(S). SHOW GEC SIZE
 AND SYSTEM, SHOW INTERSYSTEM BONDING TERMINATION POINT.
 NEC 215.5, 230, 250.50, 250.94, 408.30; FBC RE E3706.1,
 E3608.1, E3609.3; WPB FBC 107.2.1
  
 2) PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902
  
 3) IDENTIFY THE REQUIRED BATHROOM RECEPTACLE CIRCUIT IN
 THE PANEL SCHEDULE. A MINIMUM OF ONE 20 AMPERE BRANCH
 CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE
 OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS.
 PROVIDE CORRECTION. NEC 210.11(C)(3), FBC RE E3703.4
  
 4) IDENTIFY THE REQUIRED LAUNDRY RECEPTACLE CIRCUIT IN
 THE PANEL SCHEDULE. A MINIMUM OF ONE 20 AMPERE BRANCH
 CIRCUIT SHALL BE PROVIDED FOR RECEPTACLES LOCATED IN
 THE LAUNDRY AREA AND SHALL SERVE ONLY RECEPTACLE
 OUTLETS LOCATED IN THE LAUNDRY AREA. NEC 210.11(C) (2),
 FBC RE E3703.3
  
 5) THE PANEL A LOAD CALCULATIONS ARE NOT ACCURATE (USE
 RESIDENTIAL LOAD CALCUALTIONS). THE LOAD CALCULATIONS
 PROVIDED TOTAL 173.3 AMPS AND THE MAIN BUS IS SPECIFIED
 AS 150 AMPS. PROVIDE ACCURATE LOAD CALCULATION FOR
 SERVICE, INCLUDE EXISTING AND NEW LOADS TO CONFIRM
 CAPACITY OF SERVICE IS ADEQUATE. NEC 215.2, 220,
 408.30; FBC RE E3602.2
  
 6) THE ONE BATHROOM RECEPTACLE SHOWN ON THE LEFT SIDE
 OF THE TWO VANITY BASINS IS NOT ACCEPTABLE. A GFCI
 PROTECTED RECEPTACLE OUTLET ON A 20 AMP CIRCUIT IS
 REQUIRED WITHIN 3 FEET OF EACH BASIN. THE RECEPTACLE
 OUTLET SHALL BE LOCATED ON A WALL OR PARTITION THAT IS
 ADJACENT TO THE BASIN OR BASIN COUNTERTOP, LOCATED ON
 THE COUNTERTOP, OR INSTALLED ON THE SIDE OR FACE OF THE
 BASIN CABINET. PROVIDE CORRECTION. NEC 210.11(C)(3),
 210.52(D); FBC RE E3901.6
  
 7) THE ROOF FRAMING PLAN LOCATED ON SHEET A3 IS
 INCORRECTLY LABELED AS THE ELECTRICAL PLAN. FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 ROBERT MCDOUGAL
 COMBINATION PLANS EXAMINER
 561-805-6714
 [email protected]
  
  