| 2020-03-27 10:51:55 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1) SHEET A1 OF THE PLANS INDICATES THAT THE EXISTING |
| | SERVICE IS TO BE MOVED. THE ELECTRICAL PLAN ON A4 SHOWS |
| | THE SERVICE ON THE NEW BEDROOM ADDITION AND HAS IT |
| | LABELED AS EXISTING. PLEASE CORRECT. PROVIDE RISER |
| | DIAGRAM, SHOWING ALL DETAILS OF SERVICE EQUIPMENT, |
| | UNDERGROUND OR OVERHEAD SERVICE, WIRE AND BREAKER SIZES |
| | FOR SERVICE AND FEED TO ANY SUB-PANEL(S). SHOW GEC SIZE |
| | AND SYSTEM, SHOW INTERSYSTEM BONDING TERMINATION POINT. |
| | NEC 215.5, 230, 250.50, 250.94, 408.30; FBC RE E3706.1, |
| | E3608.1, E3609.3; WPB FBC 107.2.1 |
| | |
| | 2) PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| | WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5, |
| | 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902 |
| | |
| | 3) IDENTIFY THE REQUIRED BATHROOM RECEPTACLE CIRCUIT IN |
| | THE PANEL SCHEDULE. A MINIMUM OF ONE 20 AMPERE BRANCH |
| | CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE |
| | OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS. |
| | PROVIDE CORRECTION. NEC 210.11(C)(3), FBC RE E3703.4 |
| | |
| | 4) IDENTIFY THE REQUIRED LAUNDRY RECEPTACLE CIRCUIT IN |
| | THE PANEL SCHEDULE. A MINIMUM OF ONE 20 AMPERE BRANCH |
| | CIRCUIT SHALL BE PROVIDED FOR RECEPTACLES LOCATED IN |
| | THE LAUNDRY AREA AND SHALL SERVE ONLY RECEPTACLE |
| | OUTLETS LOCATED IN THE LAUNDRY AREA. NEC 210.11(C) (2), |
| | FBC RE E3703.3 |
| | |
| | 5) THE PANEL A LOAD CALCULATIONS ARE NOT ACCURATE (USE |
| | RESIDENTIAL LOAD CALCUALTIONS). THE LOAD CALCULATIONS |
| | PROVIDED TOTAL 173.3 AMPS AND THE MAIN BUS IS SPECIFIED |
| | AS 150 AMPS. PROVIDE ACCURATE LOAD CALCULATION FOR |
| | SERVICE, INCLUDE EXISTING AND NEW LOADS TO CONFIRM |
| | CAPACITY OF SERVICE IS ADEQUATE. NEC 215.2, 220, |
| | 408.30; FBC RE E3602.2 |
| | |
| | 6) THE ONE BATHROOM RECEPTACLE SHOWN ON THE LEFT SIDE |
| | OF THE TWO VANITY BASINS IS NOT ACCEPTABLE. A GFCI |
| | PROTECTED RECEPTACLE OUTLET ON A 20 AMP CIRCUIT IS |
| | REQUIRED WITHIN 3 FEET OF EACH BASIN. THE RECEPTACLE |
| | OUTLET SHALL BE LOCATED ON A WALL OR PARTITION THAT IS |
| | ADJACENT TO THE BASIN OR BASIN COUNTERTOP, LOCATED ON |
| | THE COUNTERTOP, OR INSTALLED ON THE SIDE OR FACE OF THE |
| | BASIN CABINET. PROVIDE CORRECTION. NEC 210.11(C)(3), |
| | 210.52(D); FBC RE E3901.6 |
| | |
| | 7) THE ROOF FRAMING PLAN LOCATED ON SHEET A3 IS |
| | INCORRECTLY LABELED AS THE ELECTRICAL PLAN. FBC 107.2.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. |
| | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL |
| | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. |
| | |
| | SINCERELY, |
| | |
| | ROBERT MCDOUGAL |
| | COMBINATION PLANS EXAMINER |
| | 561-805-6714 |
| | [email protected] |
| | |
| | |