| Plan Review Notes For Permit 20030477 |
| Permit Number |
20030477 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-03-12 15:27:50 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) RISER SHOWS 3 FUSES OTHER NOTES ON PLAN SHOWS | | | BREAKERS, WHICH IS IT? | | | | | | 2) FAULT CURRENT CALCULATION REQUIRED. 110.24 | | | |
|