| 2020-03-11 16:48:21 | 03/11/20 1ST GAS/ REVIEW **DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | |
| | 1. ON ISOMETRIC DRAWING THAT CLEARLY SHOWS THE LENGTH |
| | OF ALL CUT SECTIONS OF PIPE, YOU HAVE 100' BUT EACH |
| | SECTION NEED TO BE DEFINED. YOU HAE CSST BUT NOT CLEAR |
| | WHAT EACH SECTION IS FOR EACH PIPE PER THE WPB |
| | AMENDMENTS TO FBC SEC.107.2.1. |
| | |
| | 2. LISTED THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL |
| | BTU LOAD ON THE SYSTEM DOES NOT ADD UP TO YOUT TOTAL, |
| | OFF BY 20 BTU'S. REFER TO THE 2017 FBC-RES. SEC. |
| | G2413.3, G2413.4 AND TABLES G2413.4 (1) THROUGH G2413.4 |
| | (21). CONTRACTOR TO STATE WHICH TABLES ARE USED. |
| | |
| | |
| | 3. SUBMIT MANUFACTURER'S SPECIFICATION |
| | SHEETS/INSTALLATION MANUAL FOR ALL GAS GRILL EQUIPMENT |
| | TO VERIFY COMPLIANCE WITH 2017 FBC RES. SEC. G2408.1. |
| | |
| | 4. A GAS GRILL IS LABELED FOR OUTSIDE USE AND IT SEEMS |
| | TO BE IN A COVERED PATIO, IF SO PLEASE PROVIDE |
| | MANUFACTURES RECOMMENDATION FOR A VENTILATION HOOD PER |
| | THE 2017 FG 305.1 OR 2017 FBC RES. SEC. G2408.1. |
| | |
| | 5. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017 |
| | FBC FG SEC. 304.1, 614.5 (CLOTHES DRYERS AND |
| | STOVE/RANGE ) OR 2017 FBC RES. SEC. G2407.1 AND G2439.4 |
| | (CLOTHES DRYERS). |
| | |
| | 5. PLEASE SHOW THE SIZE OF THE LOUVER(S) ON THE PLANS |
| | PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 6. SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE |
| | LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION |
| | AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN |
| | RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER |
| | HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE |
| | HAND-DRAWN PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |