| 2020-03-13 11:42:18 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THERE IS AN INDICATION OF "UNDERGROUND FIRE LINE" ON | | | THE APPLICATION; HOWEVER, THERE ARE NO CLEAR | | | INDICATIONS OF WHERE THE FIRE LINE IS LOCATED NOR WHERE | | | IT WILL BE MOVED TO. | | | | | | PLEASE PROVIDE EXACT LOCATIONS OF THE FIRE LINE, HOW | | | LONG IT IS, DEPTH OF COVER, ETC, AND THAT IT WILL BE | | | INSTALLED, TESTED AND INSPECTED PER NFPA 24 | | | | | | | | | | | | 2) THERE ARE NO MANUFACTURE SPEC SHEETS FOR ANY | | | UNDERGROUND PRODUCTS. | | | | | | PLEASE PROVIDE SPEC FOR VERIFICATION PURPOSES. | | | | | | | | | | | | 3) THERE IS NO INDICATIONS OF FIRE PROTECTION DURING | | | THE INSTALL/ TRANSFER TO THE NEW LINE. | | | | | | PLEASE PROVIDE OF REVIEW OF HOW THIS WILL TAKE PLACE, | | | HOW LONG TO TRANSFER TO NEW LINE AND HOW WILL FIRE | | | PROTECTION BE PROVIDED DURING THAT TIME. | | | | | | | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|