| 2020-03-10 07:34:07 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #20030401 |
| | 3/10/20 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 201 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THIS PROJECT APPEARS TO BE A NEW INSTALLATION OF AIR |
| | CONDITIONING IN A PREVIOUSLY UNCONDITIONED SPACE. |
| | PLEASE PROVIDE A BASIC PLAN SHOWING THE LOCATIONS OF |
| | THE NEW MINI SPLIT CONDENSER AND AIR HANDLER, AND |
| | IDENTIFIY THE ROOM OR SPACE NOW BEING CONDITIONED. |
| | |
| | 2) REFER TO SECTION R503.2 FBC EC AND PROVIDE ENERGY |
| | CALACULATIONS FOR THE NEW CONDITIONED SPACE- SEE |
| | SECTION R101.5.1.1 AND PROVIDE A COMPLIANCE REPORT |
| | USING EITHER THE PRESCRIPTIVE OR PERFORMANCE BASED |
| | METHODS. |
| | |
| | 3) PROVIDE AC COOLING AND HEATING CALCULATIONS (HEAT |
| | LOADS)- SECTION R403.7 FBC EC. |
| | |
| | 4) SUBMIT AN ELECTRICAL PLAN AND AN ELECTRICAL |
| | SUB-PERMIT. PLEASE NOTE THE ELECTRICAL CONTRACT |
| | SUBMITTED WITH THE APPLICATION ALSO INDICATES |
| | INSTALLATION OF DISCONNECTS AND CIRCUITRY FOR A NW |
| | TANKLESS WATER HEATER. PLEASE NOTE THAT SEPARATE |
| | PLUMBING AND ELECTRICAL PERMITS ARE REQUIRED FOR THAT |
| | INSTALLATION- SECTION 105.1 WPB. |
| | |
| | 5) PLEASE NOTE TWO COPIES OF PLANS AND DOCUMENTS ARE |
| | REQUIRED- SECTION 107.2.1 WPB. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |