2020-03-11 15:19:50THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THE IS AN INDICATION OF NO STORAGE ON THE TOP OF THE
 CEILING; HOWEVER, THERE IS NO CEILING DETAIL.
  
 PLEASE REVIEW AND CORRECT WITH DETAILS.
  
  
  
 2) THE IS NO HEIGHT DIMENSION OF THE NEW WALL.
  
 PLEASE REVIEW AND PROVIDE.
  
  
  
 3) WHAT IS THE TYPE OF STORAGE AND HOW WILL IT BE
 PACKAGED.?
  
 PLEASE PROVIDE
  
  
  
 4) WILL SHELVING BE PROVIDED INSIDE THE STORAGE? WHAT
 TYPE, HOW HIGH?
  
 PLEASE PROVIDE.
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL