| Plan Review Notes For Permit 20030393 |
| Permit Number |
20030393 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-03-11 15:19:50 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | | | | 1) THE IS AN INDICATION OF NO STORAGE ON THE TOP OF THE | | | CEILING; HOWEVER, THERE IS NO CEILING DETAIL. | | | | | | PLEASE REVIEW AND CORRECT WITH DETAILS. | | | | | | | | | | | | 2) THE IS NO HEIGHT DIMENSION OF THE NEW WALL. | | | | | | PLEASE REVIEW AND PROVIDE. | | | | | | | | | | | | 3) WHAT IS THE TYPE OF STORAGE AND HOW WILL IT BE | | | PACKAGED.? | | | | | | PLEASE PROVIDE | | | | | | | | | | | | 4) WILL SHELVING BE PROVIDED INSIDE THE STORAGE? WHAT | | | TYPE, HOW HIGH? | | | | | | PLEASE PROVIDE. | | | | | | | | | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|