| Date |
Text |
| 2020-03-17 07:23:30 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20030393 |
| | ADD: 935 25TH COURT |
| | CONT: BIRCH CONSTRUCTION INC. |
| | TEL: 561-436-2295 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. MARCH 17TH/ 2020 |
| | ACTION: DENIED |
| | |
| | 1) ON THE PERMIT APPLICATION UNDER THE DESCRIPTION OF |
| | WORK THE DESCRIPTION OF WORK IS LISTED AS, PARTITION |
| | WALLS FOR STORAGE. PLEASE ALSO NOTE THERE IS A 4 X FEE |
| | FOR ADDING A MEZZANINE WITHOUT THE BENEFIT OF A PERMIT. |
| | THIS SCOPE OF WORK WILL ALSO BE INCLUDED IN THIS PLAN |
| | REVIEW. |
| | |
| | 1A) IT APPEARS THE CONTRACTOR HAS ELECTED TO BE THE |
| | DESIGNER OF RECORD AND WILL NEED TO SHOW COMPLIANCE |
| | WITH THE 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATIVE CODE SECTION: |
| | |
| | 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE |
| | EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H) |
| | ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C) |
| | (BUILDING) REQUIRES THE CONTRACTOR TO BE LICENSED IN |
| | THE TRADE THAT THEY WILL BE CREATING THE PLANS TO BE |
| | SUBMITTED TO THE BUILDING DEPARTMENT. FOR EACH TRADE |
| | THE CONTRACTOR RESPONSIBLE FOR THE PLAN MUST PRINT |
| | THEIR NAME, SIGN THEIR NAME AND LICENSE NUMBER. |
| | |
| | 1B) THE VALUE OF THE PERMIT IS GREATLY UNDER VALUED AT |
| | $1,000.00. 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATIVE CODE |
| | SECTION: |
| | |
| | 108.3* BUILDING PERMIT VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | 1C) 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATIVE CODE SECTION: |
| | |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING |
| | |
| | 1C)(1) TYPE OF OCCUPANCY FOR THE MAIN FLOOR LEVEL AND |
| | MEZZANINE LEVEL. STRUCTURES OR PORTIONS OF STRUCTURES |
| | SHALL BE CLASSIFIED WITH RESPECT TO OCCUPANCY IN ONE OR |
| | MORE OF THE OCCUPANCY GROUPS LISTED IN THIS SECTION. |
| | 2017 FBC-B 301.1. |
| | |
| | 1C)(2) LIST THE MINIMUM BUILDING TYPE OF CONSTRUCTION |
| | FOR THE COMBINED SQUARE FOOT AREA MAIN FLOOR LEVEL AND |
| | MEZZANINE LEVEL COMBINED. SHOW THE SQUARE FEET FOR BOTH |
| | THE FLOOR LEVEL, MEZZANINE LEVEL AND TOTAL SQUARE FOOT |
| | LEVEL. 2017 FBC-B TABLE 506.2. |
| | |
| | 1C)(3) INDICATE IF THE BUILDING IS FIRE SPRINKLERED, |
| | REQUIRES FIRE SPRINKLER? TABLE 506.2 & 903.2 WHERE |
| | REQUIRED, 2017 FBC-B. |
| | |
| | 1C)(4) LIFE SAFETY PLAN- MISSING, SHALL INCLUDE: |
| | OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| | OCCUPANCY LOAD |
| | GROSS |
| | NET |
| | MEANS OF EGRESS |
| | EXIT ACCESS |
| | |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, 6TH EDITION (2017) |
| | EXIT |
| | EXIT DISCHARGE |
| | STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION |
| | DOORS |
| | EMERGENCY LIGHTING AND EXIT SIGNS |
| | SPECIFIC OCCUPANCY REQUIREMENTS |
| | CONSTRUCTION REQUIREMENTS |
| | |
| | 1C)(5) STRUCTURAL REQUIREMENTS SHALL INCLUDE: |
| | DESIGN LOADS |
| | STRUCTURAL CALCULATIONS (MEZZANINE LEVEL) |
| | WALL SYSTEMS |
| | FLOOR SYSTEMS LIVE LOAD DESIGN |
| | STAIRS |
| | |
| | 1C) ACCESSIBILITY REQUIREMENTS ( 20 % DISPROPORTION |
| | COST) SHALL INCLUDE THE FOLLOWING: |
| | VERTICAL ACCESSIBILITY |
| | TOILET FACILITIES |
| | DRINKING FOUNTAINS |
| | |
| | 2) BUILDING A NEW MEZZANINE LEVEL MUST SHOW COMPLIANCE |
| | WITH THE 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | 2A) THE SUBMITTED PLANS CONSIST ONLY A FLOOR PLAN. |
| | PLEASE ALSO SUBMIT ELEVATIONS OF THE NEW STORAGE AREA |
| | AND THE MEZZANINE LEVEL AS WELL. PLEASE PROVIDE WHAT |
| | THE CLEAR ELEVATION OF THE STORAGE ROOM BENEATH THE |
| | MEZZANINE LEVEL. SHOW COMPLIANCE WITH THE 2017 FBC-B |
| | SECTION: |
| | 505.2 MEZZANINES. THE CLEAR HEIGHT ABOVE AND BELOW THE |
| | MEZZANINE FLOOR CONSTRUCTION SHALL NOT BE LESS THAN 7 |
| | FEET. |
| | 2B) PLEASE PROVIDE THE SIZE LIMITATIONS (AREA FOR 1ST |
| | FLOOR AND ALLOWABLE AREA OF THE MEZZANINE LEVEL) FOUND |
| | IN THE 2017 FBC-B SECTION: |
| | |
| | 2C) SHOW COMPLIANCE FOR MEANS OF EGRESS TO THE |
| | MEZZANINE LEVEL SHOW COMPLIANCE WITH THE 2017 FBC-B: |
| | |
| | 2D) SHOW THE MEZZANINE LEVEL AND AMOUNT OF OPENNESS OF |
| | THE MEZZANINE LEVEL AND COMPLIANCE WITH: |
| | |
| | 2E) FOR MEZZANINE LEVEL NEEDS TO SHOW TO WHAT LIVE LOAD |
| | THE FRAMING FOR FLOOR LOADS WAS DESIGNED TOO, SHOW |
| | COMPLIANCE WITH THE 2017 FBC-B TABLE 1607.1 (31) |
| | HEAVY 250 LBS. PER FOOT |
| | LIGHT 125 LBS. PER FOOT |
| | |
| | 2F) CITY OF WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, 6TH EDITION (2017) SECTION 106 / FLOOR |
| | AND ROOF DESIGN LOADS. |
| | |
| | 2F)(1) 106.1 LIVE LOADS POSTED. WHERE THE LIVE LOADS |
| | FOR WHICH EACH FLOOR OR PORTION THEREOF OF A |
| | COMMERCIAL OR INDUSTRIAL BUILDING IS OR HAS BEEN |
| | DESIGNED TO EXCEED 50 PSF SUCH DESIGN LIVE LOADS SHALL |
| | BE CONSPICUOUSLY POSTED BY THE OWNER IN THAT PART OF |
| | EACH STORY IN WHICH THEY APPLY, USING DURABLE SIGNS. IT |
| | SHALL BE UNLAWFUL TO REMOVE OR DEFACE SUCH NOTICES? |
| | |
| | 2F)(2) CITY OF WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | 106.2 ISSUANCE OF CERTIFICATE OF OCCUPANCY. A |
| | CERTIFICATE OF OCCUPANCY REQUIRED BY SECTION 111 |
| | SHALL NOT BE ISSUED UNTIL THE FLOOR LOAD SIGNS, |
| | REQUIRED BY SECTION 106.1, HAVE BEEN INSTALLED. |
| | |
| | 2F)(3) CITY OF WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | 106.3 RESTRICTIONS ON LOADING. IT SHALL BE UNLAWFUL TO |
| | PLACE, OR CAUSE OR PERMIT TO BE PLACED, ON ANY |
| | FLOOR OR ROOF OF A BUILDING, STRUCTURE OR PORTION |
| | THEREOF, A LOAD GREATER THAN IS PERMITTED BY THIS CODE. |
| | |
| | 3) DISPROPORTIONATE COST. 2017 FBC-ACCESSIBILITY CODE |
| | SECTION 202.4.1. PLEASE PROVIDE A LETTER EITHER FROM |
| | THE CONTRACTOR OR DESIGNER OF RECORD ON THEIR |
| | LETTERHEAD WHERE UP TO 20 % OF THE CONTRACT VALUE ($ ) |
| | IS GOING TO BE SPENT IN ACCESSIBLE UPGRADES TO THE |
| | PROJECT. IF ALL EXISTING CONDITIONS ARE COMPLETED |
| | (COMPLIED) BEFORE DISPROPORTIONATION COST IS MET A |
| | LETTER IS NOT REQUIRED. SHOW COMPLIANCE WITH THE: |
| | 2017 FBC-ACCESSIBILITY CODE SECTION 202.4.1 |
| | DISPROPORTIONATE COST. ALTERATIONS MADE TO PROVIDE AN |
| | ACCESSIBLE PATH OF TRAVEL TO THE ALTERED AREA WILL BE |
| | DEEMED DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN |
| | THE COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO |
| | THE PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS |
| | EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF |
| | TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING |
| | AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE |
| | ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING |
| | RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS, |
| | ENLARGING TOILET STALLS, INSULATING PIPES, OR |
| | INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS |
| | ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH |
| | AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT, |
| | INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT |
| | TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING |
| | AN INACCESSIBLE DRINKING FOUNTAIN. |
| | |
| | 4) PLEASE SHOW FRAMING PLAN FOR BEARING WALLS AND |
| | BEARING FLOOR JOIST. PROVIDE THE SPECIES OF WOOD, GRADE |
| | OF WOOD SPACING FOR STUDS AND FLOOR JOIST, SPAN OF |
| | FLOOR JOIST, IF MID-POINT BRACING IS TO BE INSTALLED, |
| | TYPE OF SHEATHING AND THICKNESS FOR THE SHEATHING FOR |
| | THE MEZZANINE LEVEL AND SHOW STAIR CONFIGURATION, STAIR |
| | LIVE LOAD DESIGN, TREAD & RISER DIMENSIONS, HANDRAIL |
| | AND GUARDRAIL CONFIGURATION AND LOADS TO BE DESIGNED |
| | FOR. THIS IS ALL INFORMATION THAT IS LACKING AND NEEDS |
| | TO BE INCORPORATED INTO THE DESIGN FOR THIS PERMIT. |
| | 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 5) PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. |
| | CALL (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT |
| | ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE |
| | RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS |
| | APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE |
| | QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE |
| | FORM CAN BE FOUND AT: |
| | HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPAC |
| | TFEES/FORMS/QUESTIONNAIRE.PDF |
| | |
| | 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | |
| | JAMES A. WITMER BN, PX, SFP & CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |