2020-03-24 15:50:461ST REVIEW FBC-2017 MECHANICAL
 PERMIT #20030359
 3/24/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 COMMENT #3 PRINTED BELOW FROM THE 1ST REVIEW STILL
 EXISTS- PLEASE COMPLY.
  
 3) THE $1000.00 VALUE ON THE PERMIT APPLICATION APPEARS
 TO BE FOR LABOR ONLY. THERE IS A SECOND PERMIT
 SUBMITTED #20030358 FOR GAS PIPING CONNECTION WITH A
 $750.00 VALUE WHICH ALSO APPEARS TO BE LABOR ONLY.
 PLEASE NOTE IN ACCORDANCE WITH SECTION 109.3 WPB,
 PERMIT VALUE IS BASED ON LABOR, MATERIALS, EQUIPMENT,
 APPLIANCES, FIXTURES, DESIGN FEES AND SITE WORK. PLEASE
 UPDATE THE PERMIT VALUES ON EACH APPLICATION TO INCLUDE
 THE COST OF THE DRYERS, AND ANY NEW WORK THAT WILL HAVE
 TO BE ACCOMPLISHED FOR CODE COMPLIANT INSTALLATIONS.
  
 NEW COMMENTS.
  
 1) SIGNATURE OF CONTRACTOR OR QUALIFIER ON PLANS
 REQUIRED- SEE FLORIDA STATUTE 633.021, AND SECTION
 107.2.1 FBC. WPB AMENDMENTS TO THE FBC: ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
  
 2) THE SUBMITTED PHOTOS SHOW ONE OF THE DRYER EXHAUST
 DUCTS MAKING A HORIZONTAL PENETRATION THROUGH ONE OF
 THE MAKEUP AIR VENTS. THE DUCT IS REDUCING THE REQUIRED
 AIR INLET OPENING SIZE AND NEEDS TO BE REROUTED-
 SECTION 304.6 FBC FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  