| 2020-03-13 08:10:52 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #20030359 |
| | 3/12/20 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE NEW DRYERS SHALL BE INSTALLED AND EXHAUSTED IN |
| | ACCORDANCE WITH THE MANUFACTURER'S GUIDELINES- SECTION |
| | 504.1 FBC M. PLEASE SUBMIT TWO COMPLETE COPIES OF THE |
| | SPECIFICATIONS AND INSTALLATION INSTRUCTIONS. |
| | |
| | 2) IN ORDER TO VERIFY THAT THE EXISTING DRYER EXHAUST |
| | DUCTS ARE 8" DIAMETER ACCORDING TO THE GUIDELINES, AND |
| | THAT ADEQUATE COMBUSTION AND MAKEUP AIR IS BEING |
| | PROVIDED TO THE DRYERS, PLEASE SUBMIT DRAWINGS AND |
| | DETAILS SHOWING THE FOLLOWING ITEMS: |
| | |
| | A) THE TYPE AND SIZE OF EXISTING EXHAUST DUCTS |
| | INCLUDING THEIR TOTAL LENGTH RUNS AND TERMINATION |
| | LOCATIONS- SECTION 504.8- 504.8.4.2 FBC M. |
| | |
| | B) COMBUSTION AIR CALCULATIONS AND HOW COMBUSTION AIR |
| | IS BEING PROVIDED- WHCH METHOD IS BEING USED- SEE |
| | SECTION 304 FBC FG. PLEASE NOTE THE SUBMITTED SPECS |
| | REQUIRE 1.5 SQ. FT. OF MAKE UP AIR OPENING FOR EACH |
| | STACK DRYER. |
| | |
| | C) REQUIRED CLEARANCES AT THE BACK AND SIDES OF THE |
| | DRYERS PER THE SPECS. |
| | |
| | 3) THE $1000.00 VALUE ON THE PERMIT APPLICATION APPEARS |
| | TO BE FOR LABOR ONLY. THERE IS A SECOND PERMIT |
| | SUBMITTED #20030358 FOR GAS PIPING CONNECTION WITH A |
| | $750.00 VALUE WHICH ALSO APPEARS TO BE LABOR ONLY. |
| | PLEASE NOTE IN ACCORDANCE WITH SECTION 109.3 WPB, |
| | PERMIT VALUE IS BASED ON LABOR, MATERIALS, EQUIPMENT, |
| | APPLIANCES, FIXTURES, DESIGN FEES AND SITE WORK. PLEASE |
| | UPDATE THE PERMIT VALUES ON EACH APPLICATION TO INCLUDE |
| | THE COST OF THE DRYERS, AND ANY NEW WORK THAT WILL HAVE |
| | TO BE ACCOMPLISHED FOR CODE COMPLIANT INSTALLATIONS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |