| 2020-03-10 19:11:06 | 3/10/2020 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1-SUBMIT COMPLETE MANUFACTURER'S SPECIFICATIONS FOR THE |
| | GAS DRYER. THE GAS DRYER SHALL BE LISTED AND LABELED |
| | PER THE 2017 FBC FUEL GAS SEC.301.3 OR 2017 FBC FUEL |
| | GAS RES. SEC. G2404.3. THE MANUFACTURER'S |
| | SPECIFICATIONS SHALL NOTE THE CFM'S THAT ARE BEING |
| | EXHAUSTED BY THE DRYER. |
| | |
| | 2-GAS RISER DIAGRAM REQUIRED WPB AMENDMENTS TO THE FBC |
| | SEC. 107.5.1.5 (9) COMMERCIAL GAS |
| | |
| | 3-SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED GAS |
| | APPLIANCES. WHERE IS COMBUSTION AIR PROVIDED BY THE |
| | BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM |
| | SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN |
| | ADDITION TO THE REQUIRED VENTILATION AIR? 2017 FGC |
| | SEC.304.9.3 OR 2017 FBC R G2407.9.3. COMBINED |
| | COMBUSTION AIR AND VENTILATION AIR SYSTEM. |
| | |
| | 4-THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON THE |
| | APPLICATION, PLEASE PROVIDE A BONA FIDE SIGNED |
| | CONTRACT. WPB AMENDMENTS TO THE FBC SEC. 109.3 BUILDING |
| | PERMIT VALUATIONS. |
| | |
| | 5-I HAVE RESEARCHED CITY RECORDS BACK TO 0000 AND THERE |
| | IS NO RECORD OF A PERMIT FOR THE INSTALLATION OF ANY |
| | GAS ON THIS ADDRESS. WPB AMENDMENTS TO THE FBC SEC. |
| | 105.1. |
| | |
| | 6-SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE |
| | LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC FUEL |
| | GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC FUEL GAS RES |
| | SECS. G2413.4.1, G2413.4.2. |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | ATELYO BELISLE |
| | PLUMBING INSPECTOR / |
| | PLUMBING PLAN REVIEW |
| | AVAILABLE FROM 1:00 PM TO 4:00 PM |
| | [email protected] |
| | 561-805-6695 |
| | |