| 2020-05-08 09:46:43 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA SHALL BEAR THE PRINTED NAME AND |
| | SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. |
| | |
| | 2) |
| | |
| | 3) |
| | |
| | 4) |
| | |
| | 5) SEVERAL OF THE REMODELED AREAS AND THE NEWLY |
| | ENCLOSED AREAS DO NOT COMPLY WITH THE WALL SPACING |
| | REQUIREMENTS FOR RECEPTACLE OUTLETS. RECEPTACLES SHALL |
| | BE INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY |
| | ALONG THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 |
| | FEET FROM A RECEPTACLE OUTLET. PROVIDE CORRECTION. NEC |
| | 210.52; FBC RE E3901.2.1 PROPOSED GREAT ROOM AND BAR |
| | ARE |
| | |
| | |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. |
| | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL |
| | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. |
| | |