| | 2ND BUILDING REVIEW DENIED: |
| | |
| | 1. FBC B 107.2.1, THE ARCHITECTUAL DRAWINGS DO NOT HAVE |
| | THE DESIGNER'S NAME AND SIGNATURE. |
| | THE CONSTRUCTION DOCUMENTS SHALL BE PREPARED BY A |
| | REGISTERED DESIGN PROFESSIONAL WHERE REQUIRED BY |
| | CHAPTER 471, FLORIDA STATUTES & 61G15 FLORIDA |
| | ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA STATUTES & |
| | 61G1 FLORIDA ADMINISTRATIVE CODE. |
| | |
| | 2. FBC B 107.2.1 INDICATE WHERE THE WINDOW WALL SYSTEM |
| | ( NOA NO.19-0326.07 ) WILL BE INSTALLED. |
| | |
| | 3. FBC B 107.2.1 PLEASE CLARIFY IF THE STEEL PLATE |
| | CONNECTION DETAIL 13/S2 REQUIRES FASTENER SPACING OF |
| | 12" OR 16" O.C. |
| | |
| | 4. FBC B 107.2.1 PLEASE CLARIFY THE WELD SIZES ON PAGES |
| | S-2 AND S-3.1 AS THE DETAILS CALL FOR ALL AROUND FILLET |
| | WELDS, 1" WELD SIZE/THICKNESS. THAT WELD SIZE IS |
| | THICKER THAN THE BASE MATERIALS. |
| | |
| | IN ADDITION TO CORRECTING THE WELD SIZE ON THE PLANS, |
| | AT TIME OF INSPECTION PLEASE PROVIDE THE FOLLOWING: |
| | AWS D1.1 CLAUSE 3.1: AT TIME OF INSPECTION PLEASE |
| | PROVIDE A WELD PROCEDURE SPECIFICATION; THE W.P.S. |
| | SPECIFIES THE REQUIRED ESSENTIAL VARIABLES INCLUDING: |
| | BASE MATERIALS, JOINTS, PROCESS, AND FILLER METALS TO |
| | BE USED. |
| | AWS D1.1 CLAUSE 4.15: AT TIME OF INSPECTION PLEASE |
| | PROVIDE A WELDER PERFORMANCE QUALIFICATION RECORD; THE |
| | W.P.Q.R. PROVIDES INFORMATION WHICH CAN BE USED TO |
| | VERIFY THE WELDER?S QUALIFICATION AND CERTIFICATION AS |
| | IT RELATES TO THE WELDING REQUIREMENTS OF THE PROJECT. |
| | |