2020-03-21 16:23:38ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. DISCONNECT WITH OVERCURRENT PROTECTION NEEDED
 BETWEEN COMBINER BOX AND METER/MAIN COMBO. ELECTRIC
 POWER PRODUCTION SYSTEM MUST HAVE OCP WITHIN 10FT WHEN
 INTERCONNECTING TO PRIMARY POWER SUPPLY ON LOAD SIDE OF
 SERVICE DISCONNECTING MEANS. NEC 705.31
  
 2. BACK FED PV BREAKER IN METER/MAIN COMBO MUST BE AT
 OPPOSITE END OF BUS BAR. NEC 705.12(D)(2)(3)(B)
  
 END OF COMMENTS.
  