| 2020-03-09 12:40:01 | 03/09/2020 PLUMBING 1ST REVIEW **DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | 1. THE FIRE SPRINKLER SYSTEM DOUBLE CHECK DETECTOR |
| | ASSEMBLY REQUIRES TO BE INSTALLED BY A LICENSED |
| | CONTRACTOR PER THE 2017 FLORIDA STATUTES 633.102, |
| | INSURANCE, CHAPTER 633, FIRE PREVENTION AND CONTROL, 3 |
| | (A) CONTRACTOR I, II AND V ARE THE ONLY ONE'S LICENSED |
| | CONTRACTOR WHOSE BUSINESS INCLUDES THE EXECUTION OF |
| | CONTRACTS REQUIRING THE ABILITY TO LAYOUT, FABRICATE, |
| | INSTALL, INSPECT, ALTER, REPAIR, AND SERVICE ALL TYPES |
| | OF FIRE PROTECTION SYSTEMS, EXCLUDING PRE-ENGINEERED |
| | SYSTEMS AND THIS NEEDS TO BE CERTIFIED BY THE UTILITIES |
| | DEPARTMENT. THIS IS A CONTAINMENT DEVICE AS THE CITY OF |
| | WEST PALM BEACH UTILITIES DEPARTMENT HAS JURISDICTION |
| | OF IT AND NEEDS TO BE CERTIFIED BY THEM. |
| | |
| | 2. A GENERAL CONTRACTOR OR AN UNDERGROUND UTILITY AND |
| | EXCAVATION CONTRACTOR CANNOT INSTALL A BACKFLOW DEVICE |
| | PER THE 2019 FLORIDA STATUTES TITLE XXXII CHAPTER |
| | 489.105(N). PLEASE PROVIDE THE PERMITTING DEPARTMENT |
| | WITH A VALID STATE OF FLORIDA LICENSED CONTRACTOR ALONG |
| | WITH AN APPLICATION. |
| | |
| | FS 489.105 DEFINITIONS.-- AS USED IN THIS PART: |
| | |
| | (1) "BOARD" MEANS THE CONSTRUCTION INDUSTRY LICENSING |
| | BOARD. |
| | (2) "DEPARTMENT" MEANS THE DEPARTMENT OF BUSINESS AND |
| | PROFESSIONAL REGULATION. |
| | (3) "CONTRACTOR" MEANS THE PERSON WHO IS QUALIFIED FOR, |
| | AND IS ONLY RESPONSIBLE FOR, THE PROJECT. |
| | |
| | (N) "UNDERGROUND UTILITY AND EXCAVATION CONTRACTOR" |
| | MEANS A CONTRACTOR WHOSE SERVICES ARE LIMITED TO THE |
| | CONSTRUCTION, INSTALLATION, AND REPAIR, ON PUBLIC OR |
| | PRIVATE PROPERTY, WHETHER ACCOMPLISHED THROUGH OPEN |
| | EXCAVATIONS OR THROUGH OTHER MEANS, INCLUDING, BUT NOT |
| | LIMITED TO, DIRECTIONAL DRILLING, AUGER BORING, JACKING |
| | AND BORING, TRENCHLESS TECHNOLOGIES, WET AND DRY TAPS, |
| | GROUTING, AND SLIP LINING, OF MAIN SANITARY SEWER |
| | COLLECTION SYSTEMS, MAIN WATER DISTRIBUTION SYSTEMS, |
| | STORM SEWER COLLECTION SYSTEMS, AND THE CONTINUATION OF |
| | UTILITY LINES FROM THE MAIN SYSTEMS TO A POINT OF |
| | TERMINATION UP TO AND INCLUDING THE METER LOCATION FOR |
| | THE INDIVIDUAL OCCUPANCY, SEWER COLLECTION SYSTEMS AT |
| | PROPERTY LINE ON RESIDENTIAL OR SINGLE-OCCUPANCY |
| | COMMERCIAL PROPERTIES, OR ON MULTIOCCUPANCY PROPERTIES |
| | AT MANHOLE OR WYE LATERAL EXTENDED TO AN INVERT |
| | ELEVATION AS ENGINEERED TO ACCOMMODATE FUTURE BUILDING |
| | SEWERS, WATER DISTRIBUTION SYSTEMS, OR STORM SEWER |
| | COLLECTION SYSTEMS AT STORM SEWER STRUCTURES. HOWEVER, |
| | AN UNDERGROUND UTILITY AND EXCAVATION CONTRACTOR MAY |
| | INSTALL EMPTY UNDERGROUND CONDUITS IN RIGHTS-OF-WAY, |
| | EASEMENTS, PLATTED RIGHTS-OF-WAY IN NEW SITE |
| | DEVELOPMENT, AND SLEEVES FOR PARKING LOT CROSSINGS NO |
| | SMALLER THAN 2 INCHES IN DIAMETER IF EACH CONDUIT |
| | SYSTEM INSTALLED IS DESIGNED BY A LICENSED PROFESSIONAL |
| | ENGINEER OR AN AUTHORIZED EMPLOYEE OF A MUNICIPALITY, |
| | COUNTY, OR PUBLIC UTILITY AND THE INSTALLATION OF SUCH |
| | CONDUIT DOES NOT INCLUDE INSTALLATION OF ANY CONDUCTOR |
| | WIRING OR CONNECTION TO AN ENERGIZED ELECTRICAL SYSTEM. |
| | AN UNDERGROUND UTILITY AND EXCAVATION CONTRACTOR MAY |
| | NOT INSTALL PIPING THAT IS AN INTEGRAL PART OF A FIRE |
| | PROTECTION SYSTEM AS DEFINED IN S. 633.102 BEGINNING AT |
| | THE POINT WHERE THE PIPING IS USED EXCLUSIVELY FOR SUCH |
| | SYSTEM. |
| | |
| | 3. THE RPZ DEVICE REQUIRES A PERMIT REQUIRED BY A |
| | LICENSED CONTRACTOR AND MUST BE CERTIFIED BY UTILITIES |
| | PRIOR TO FINAL INSPECTION. PLEASE CONTACT THE CITY OF |
| | WPB UTILITIES AT 561-822-2240 FOR FURTHER DIRECTIONS. |
| | |
| | 4. YOU WILL NEED TO SUBMIT TWO SEPARATE APPLICATION FOR |
| | BOTH BACKFLOW AS THE CANNOT BE COMBINED. THE FIRE IS |
| | ONE AND YOU MAY COMBINE WATER MAIN, IRRIGATION AND |
| | WATER FEATURES INTO THE SECOND PERMIT AS NOTE ABOVE DUE |
| | TO ITS SPECIALTIES. PLEASE FEEL FREE TO CONTACT ME OR |
| | MY CHIEF PLUMBING INSPECTOR TIM LARGE @ 561 805-6692 OR |
| | MY SELF SEE BELOW. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |