| 2020-03-13 10:55:40 | CODES IN EFFECT: |
| | |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED |
| | |
| | ORIGINAL PERMIT # 19091103 SHOWED A 4 BEDROOM HOUSE. |
| | THE ENERGY CALCULATIONS AND THE MECHANICAL SHEET |
| | MATCHED. THIS REVISION #20030292 NOW SHOWS A 5 BEDROOM |
| | HOUSE. THE ROOMS NOW DO NOT MATCH THE ENERGY |
| | CALCULATIONS. THE DUCT SIZES DO NOT MATCH, THERE ISN?T |
| | A WALKIN CLOSET BUT THE ENERGY CALCULATIONS CALLS OUT A |
| | DUCT IN THE MASTER CLOSET. PLEASE PROVIDE AN ENERGY |
| | CALCULATION THAT MATCHES THIS 5 BEDROOM HOUSE. |
| | |
| | CODE SECTION: FBC EC 107.2 CONSTRUCTION DOCUMENTS. |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |