 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) DRAWING A300 SHOWS CEILING HEIGHT AT 6 FOOT 8
 INCHES. PLEASE SHOW CEILING HEIGHT TO COMPLY WITH FBC
 R305.1 (SPACE IS HABITABLE MINIMUM CEILING HEIGHT 7
 FEET)
 2) PLEASE SHOW CEILING INSULATION TYPE AND "R" VALUE.
 FBC ENERGY R401.1
 3) DRAWING A300 SHOWS SOFFIT SCREEN VENT AT 8-FOOT OC.
 SHOULD BE A CONTINUOUS SCREEN VENT FOR ENCLOSED RAFTER
 SPACES FBC R806
 4) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR DOOR AND WINDOWS.
 5) PLEASE SHOW THE BUILDING SET BACK FROM THE PROPERTY
 LINE AT THE NORTH EAST CORNER OF THE BUILDING. FBC
 TABLE R302.1 (NEEDED TO DETERMINE THE FIRE RATING - IF
 ANY)
 6) SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED.
  