Plan Review Notes
Plan Review Notes For Permit 20030157
Permit Number 20030157
Review Stop M
Sequence Number 1
Notes
Date Text
2020-03-13 13:35:531ST REVIEW FBC-2017 MECHANICAL
 PERMIT 20030157
  
 CODES IN EFFECT:
  
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 THIS PROJECT APPEARS TO BE ADDING ADDITIONAL
 CONDITIONED SQUARE FOOTAGE. PLEASE PROVIDE THE REQUIRE
 INFORMATION ON THESE PLANS. SHOW WHERE THE HVAC SYSTEM
 IS LOCATED FOR THIS ADDITION. ATTACH SPEC SHEETS FOR
 THIS SYSTEM. PROVIDE SPEC SHEETS FOR THE BATH EXHAUST
 FAN. SHOW LOCATION OF EXHAUST TERMINATION. SHOW
 LOCATION OF CONDENSING UNIT. PROVIDE ENERGY
 CALCULATIONS FOR THIS ADDITION.
 SEE FBC EC R103.2 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DRAWN TO SCALE UPON
 SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE
 PERMITTED TO BE SUBMITTED WHERE APPROVED BY THE CODE
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED, AND SHOW IN SUFFICIENT DETAIL
 PERTINENT DATA AND FEATURES OF THE BUILDING, SYSTEMS
 AND EQUIPMENT AS HEREIN GOVERNED. DETAILS SHALL
 INCLUDE, BUT ARE NOT LIMITED TO, THE FOLLOWING AS
 APPLICABLE:
 1.INSULATION MATERIALS AND THEIR R-VALUES.
 2.FENESTRATION U-FACTORS AND SOLAR HEAT GAIN
 COEFFICIENTS (SHGC).
 3.AREA-WEIGHTED U-FACTOR AND SOLAR HEAT GAIN
 COEFFICIENTS (SHGC) CALCULATIONS.
 4.MECHANICAL SYSTEM DESIGN CRITERIA.
 5.MECHANICAL AND SERVICE WATER-HEATING SYSTEM AND
 EQUIPMENT TYPES, SIZES AND EFFICIENCIES.
 6.EQUIPMENT AND SYSTEM CONTROLS.
 7.DUCT SEALING, DUCT AND PIPE INSULATION AND LOCATION.
 8.AIR SEALING DETAILS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  