| 2020-03-10 14:36:04 | PERMIT # 20030129 |
| | |
| | CODES IN EFFECT: |
| | |
| | 2017 EDITIONS OF: |
| | FBC RE = FLORIDA RESIDENTIAL CODE, 6TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION, 6TH |
| | EDITION |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL PLANS EXAMINER II |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6728 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | RESULTS: DENIED |
| | |
| | |
| | |
| | |
| | 1) THE CONSTRUCTION SERVICES DIVISION DOES NOT HAVE A |
| | RECORD OF A PRE-EXISTING HVAC SYSTEM AT THIS ADDRESS. |
| | AMEND THE ORIGINAL PERMIT TO REFLECT THAT THIS IS A NEW |
| | INSTALLATION INTO AN EXISTING STRUCTURE. |
| | |
| | (FBC RE CHAPTER 1 FBC ADMINISTRATION (SECTION 105) |
| | 105.1 REQUIRED. ANY CONTRACTOR, OWNER, OR AGENT |
| | AUTHORIZED IN ACCORDANCE WITH FLORIDA STATUTE 489 WHO |
| | INTENDS TO CONSTRUCT, ENLARGE, ALTER, REPAIR, MOVE, |
| | DEMOLISH, OR CHANGE THE OCCUPANCY OF A BUILDING OR |
| | STRUCTURE, OR TO ERECT, INSTALL, ENLARGE, ALTER, |
| | REPAIR, REMOVE, CONVERT OR REPLACE ANY IMPACT-RESISTANT |
| | COVERINGS, ELECTRICAL, GAS, MECHANICAL, PLUMBING OR |
| | FIRE PROTECTION SYSTEM, OR ACCESSIBLE OR FLOOD |
| | RESISTANT SITE ELEMENT, THE INSTALLATION OF WHICH IS |
| | REGULATED BY THIS CODE, OR TO CAUSE ANY SUCH WORK TO BE |
| | DONE, SHALL FIRST MAKE APPLICATION TO THE BUILDING |
| | OFFICIAL AND OBTAIN THE REQUIRED PERMIT. |
| | THE CONSTRUCTION SERVICES DIVISION DOES NOT HAVE A |
| | RECORD OF A PRE-EXISTING HVAC SYSTEM AT THIS ADDRESS. |
| | AMEND THE ORIGINAL PERMIT TO REFLECT THAT THIS IS A NEW |
| | INSTALLATION INTO AN EXISTING STRUCTURE. |
| | |
| | |
| | FBC CE R503.2CHANGE IN SPACE CONDITIONING. |
| | ANY NONCONDITIONED OR LOW-ENERGY SPACE THAT IS ALTERED |
| | TO BECOME CONDITIONED SPACE SHALL BE REQUIRED TO BE |
| | BROUGHT INTO FULL COMPLIANCE WITH THIS CODE. |
| | EXCEPTION: WHERE THE SIMULATED PERFORMANCE OPTION IN |
| | SECTION R405 IS USED TO COMPLY WITH THIS SECTION, THE |
| | ANNUAL ENERGY COST OF THE PROPOSED DESIGN IS PERMITTED |
| | TO BE 110 PERCENT OF THE ANNUAL ENERGY COST OTHERWISE |
| | ALLOWED BY SECTION R405.3) |
| | |
| | 2) PLEASE PROVIDE CALCULATIONS FROM ACCA MANUAL J, S |
| | AND D. |
| | FBC CHAPTER 1 ADMINISTRATION- 107.3.5 MINIMUM PLAN |
| | REVIEW CRITERIA FOR BUILDINGS -107.3.5.1.4 MECHANICAL; |
| | ALSO SEE FBC CE SECTION R403.7 PLEASE PROVIDE |
| | CALCULATIONS FROM ACCA MANUAL J |
| | |
| | 3) DUCT INSULATION SHALL MEET: FBC CE SECTION- |
| | R403.3.1INSULATION (PRESCRIPTIVE). |
| | SUPPLY AND RETURN DUCTS IN ATTICS SHALL BE INSULATED TO |
| | A MINIMUM OF R-8 WHERE 3 INCHES (76 MM) IN DIAMETER AND |
| | GREATER AND R-6 WHERE LESS THAN 3 INCHES (76 MM) IN |
| | DIAMETER. SUPPLY AND RETURN DUCTS IN OTHER PORTIONS OF |
| | THE BUILDING SHALL BE INSULATED TO A MINIMUM OF R-6 |
| | WHERE 3 INCHES (76 MM) IN DIAMETER OR GREATER AND R-4.2 |
| | WHERE LESS THAN 3 INCHES (76 MM) IN DIAMETER. |
| | EXCEPTION: DUCTS OR PORTIONS THEREOF LOCATED COMPLETELY |
| | INSIDE THE BUILDING THERMAL ENVELOPE. |
| | |
| | |
| | 4) PLEASE SUBMIT DRAWINGS AND A SUB PERMIT FOR THE NEW |
| | ELECTRICAL FOR THIS HVAC SYSTEM. |
| | PLEASE AMEND THE ORIGINAL MECHANICAL PERMIT TO REFLECT |
| | THE COST OF THE ELECTRICAL WORK FOR THIS HVAC |
| | INSTALLATION. |
| | (FBC RE CHAPTER 1 FBC ADMINISTRATION (SECTION 105) |
| | 105.1 REQUIRED. ANY CONTRACTOR, OWNER, OR AGENT |
| | AUTHORIZED IN ACCORDANCE WITH FLORIDA STATUTE 489 WHO |
| | INTENDS TO CONSTRUCT, ENLARGE, ALTER, REPAIR, MOVE, |
| | DEMOLISH, OR CHANGE THE OCCUPANCY OF A BUILDING OR |
| | STRUCTURE, OR TO ERECT, INSTALL, ENLARGE, ALTER, |
| | REPAIR, REMOVE, CONVERT OR REPLACE ANY IMPACT-RESISTANT |
| | COVERINGS, ELECTRICAL, GAS, MECHANICAL, PLUMBING OR |
| | FIRE PROTECTION SYSTEM, OR ACCESSIBLE OR FLOOD |
| | RESISTANT SITE ELEMENT, THE INSTALLATION OF WHICH IS |
| | REGULATED BY THIS CODE, OR TO CAUSE ANY SUCH WORK TO BE |
| | DONE, SHALL FIRST MAKE APPLICATION TO THE BUILDING |
| | OFFICIAL AND OBTAIN THE REQUIRED PERMIT.) |
| | |
| | 5) DESIGNER MUST SIGN AND PRINT NAME ON THE DRAWINGS. |
| | FBC CHAPTER 1 ADMINISTRATION- 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE |
| | DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. |
| | ELECTRONIC MEDIA DOCUMENTS SHALL BE |
| | SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL. |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE WORK PROPOSED AND SHOW IN DETAIL |
| | THAT IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND |
| | REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. |
| | SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| | AS TO THE QUALITY OF MATERIALS, WHERE |
| | QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL |
| | CODES. SUCH INFORMATION SHALL BE SPECIFIC, |
| | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE |
| | OR IN PART, NOR SHALL THE TERM "LEGAL" OR |
| | ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION. ALL INFORMATION, DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE |
| | NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR THE DESIGN. (SEE ALSO SECTION 107.3.5). |
| | |
| | |
| | |