2020-03-10 14:36:04PERMIT # 20030129
  
 CODES IN EFFECT:
  
 2017 EDITIONS OF:
 FBC RE = FLORIDA RESIDENTIAL CODE, 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION, 6TH
 EDITION
  
 MICHAEL EDWARDS
 MECHANICAL PLANS EXAMINER II
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6728
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
  
  
  
  
 1) THE CONSTRUCTION SERVICES DIVISION DOES NOT HAVE A
 RECORD OF A PRE-EXISTING HVAC SYSTEM AT THIS ADDRESS.
 AMEND THE ORIGINAL PERMIT TO REFLECT THAT THIS IS A NEW
 INSTALLATION INTO AN EXISTING STRUCTURE.
  
 (FBC RE CHAPTER 1 FBC ADMINISTRATION (SECTION 105)
 105.1 REQUIRED. ANY CONTRACTOR, OWNER, OR AGENT
 AUTHORIZED IN ACCORDANCE WITH FLORIDA STATUTE 489 WHO
 INTENDS TO CONSTRUCT, ENLARGE, ALTER, REPAIR, MOVE,
 DEMOLISH, OR CHANGE THE OCCUPANCY OF A BUILDING OR
 STRUCTURE, OR TO ERECT, INSTALL, ENLARGE, ALTER,
 REPAIR, REMOVE, CONVERT OR REPLACE ANY IMPACT-RESISTANT
 COVERINGS, ELECTRICAL, GAS, MECHANICAL, PLUMBING OR
 FIRE PROTECTION SYSTEM, OR ACCESSIBLE OR FLOOD
 RESISTANT SITE ELEMENT, THE INSTALLATION OF WHICH IS
 REGULATED BY THIS CODE, OR TO CAUSE ANY SUCH WORK TO BE
 DONE, SHALL FIRST MAKE APPLICATION TO THE BUILDING
 OFFICIAL AND OBTAIN THE REQUIRED PERMIT.
 THE CONSTRUCTION SERVICES DIVISION DOES NOT HAVE A
 RECORD OF A PRE-EXISTING HVAC SYSTEM AT THIS ADDRESS.
 AMEND THE ORIGINAL PERMIT TO REFLECT THAT THIS IS A NEW
 INSTALLATION INTO AN EXISTING STRUCTURE.
  
  
 FBC CE R503.2CHANGE IN SPACE CONDITIONING.
 ANY NONCONDITIONED OR LOW-ENERGY SPACE THAT IS ALTERED
 TO BECOME CONDITIONED SPACE SHALL BE REQUIRED TO BE
 BROUGHT INTO FULL COMPLIANCE WITH THIS CODE.
 EXCEPTION: WHERE THE SIMULATED PERFORMANCE OPTION IN
 SECTION R405 IS USED TO COMPLY WITH THIS SECTION, THE
 ANNUAL ENERGY COST OF THE PROPOSED DESIGN IS PERMITTED
 TO BE 110 PERCENT OF THE ANNUAL ENERGY COST OTHERWISE
 ALLOWED BY SECTION R405.3)
  
 2) PLEASE PROVIDE CALCULATIONS FROM ACCA MANUAL J, S
 AND D.
 FBC CHAPTER 1 ADMINISTRATION- 107.3.5 MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS -107.3.5.1.4 MECHANICAL;
 ALSO SEE FBC CE SECTION R403.7 PLEASE PROVIDE
 CALCULATIONS FROM ACCA MANUAL J
  
 3) DUCT INSULATION SHALL MEET: FBC CE SECTION-
 R403.3.1INSULATION (PRESCRIPTIVE).
 SUPPLY AND RETURN DUCTS IN ATTICS SHALL BE INSULATED TO
 A MINIMUM OF R-8 WHERE 3 INCHES (76 MM) IN DIAMETER AND
 GREATER AND R-6 WHERE LESS THAN 3 INCHES (76 MM) IN
 DIAMETER. SUPPLY AND RETURN DUCTS IN OTHER PORTIONS OF
 THE BUILDING SHALL BE INSULATED TO A MINIMUM OF R-6
 WHERE 3 INCHES (76 MM) IN DIAMETER OR GREATER AND R-4.2
 WHERE LESS THAN 3 INCHES (76 MM) IN DIAMETER.
 EXCEPTION: DUCTS OR PORTIONS THEREOF LOCATED COMPLETELY
 INSIDE THE BUILDING THERMAL ENVELOPE.
  
  
 4) PLEASE SUBMIT DRAWINGS AND A SUB PERMIT FOR THE NEW
 ELECTRICAL FOR THIS HVAC SYSTEM.
 PLEASE AMEND THE ORIGINAL MECHANICAL PERMIT TO REFLECT
 THE COST OF THE ELECTRICAL WORK FOR THIS HVAC
 INSTALLATION.
 (FBC RE CHAPTER 1 FBC ADMINISTRATION (SECTION 105)
 105.1 REQUIRED. ANY CONTRACTOR, OWNER, OR AGENT
 AUTHORIZED IN ACCORDANCE WITH FLORIDA STATUTE 489 WHO
 INTENDS TO CONSTRUCT, ENLARGE, ALTER, REPAIR, MOVE,
 DEMOLISH, OR CHANGE THE OCCUPANCY OF A BUILDING OR
 STRUCTURE, OR TO ERECT, INSTALL, ENLARGE, ALTER,
 REPAIR, REMOVE, CONVERT OR REPLACE ANY IMPACT-RESISTANT
 COVERINGS, ELECTRICAL, GAS, MECHANICAL, PLUMBING OR
 FIRE PROTECTION SYSTEM, OR ACCESSIBLE OR FLOOD
 RESISTANT SITE ELEMENT, THE INSTALLATION OF WHICH IS
 REGULATED BY THIS CODE, OR TO CAUSE ANY SUCH WORK TO BE
 DONE, SHALL FIRST MAKE APPLICATION TO THE BUILDING
 OFFICIAL AND OBTAIN THE REQUIRED PERMIT.)
  
 5) DESIGNER MUST SIGN AND PRINT NAME ON THE DRAWINGS.
 FBC CHAPTER 1 ADMINISTRATION- 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE
 SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL
 THAT IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
 SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL
 CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN. (SEE ALSO SECTION 107.3.5).
  
  
  