| Plan Review Notes For Permit 20030124 |
| Permit Number |
20030124 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-04-06 10:39:39 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | BUILDING PLAN REVIEW DENIED: | | | | | | FBC B 107.2.2, AS PER LAST BUILDING REVIEW ITEM #5; THE | | | INFORMATION ON SHEET G-103B NEEDS TO BE CORRECTED. | | | PLEASE CHANGE THE CONSTRUCTION TYPE LISTED IN TYPES OF | | | CONSTRUCTION (A) CH.6, LAST COLUMN AT TOP ROW SHOWS | | | TYPE 2B. THE FIRST COLUMN SHOWS TYPE 1B, THESE TWO | | | COLUMNS NEED TO MATCH. | | | | | | | | | | | | | | | NOTE: AS PER LAST REVIEW, NO RESPONSE NEEDED FOR | | | PROVISOS THEY WILL BE | | | ADDED TO PLANS BEFORE BEING ISSUED. | | | | | | A) PROVIDE PRODUCT APPROVAL FOR ROOF HATCH AND LADDER | | | WITH 16 SQ. FT MINUMUM OPENING | | | AS REQUIRED BY FBC 1011.12 AND 1011.12.1 | | | | | | B) ENGINEERING FOR HANDRAILS AND GUARDRAILS. | | | | | | C) SUBMITTAL TO INCLUDE ANY PRODUCT APPROVALS INCLUDING | | | WINDOWS, STOREFRONT AND DOORS. | | | | | | D) ROOFING PRODUCT APPROVALS TO BE SUBMITTED WITH SUB | | | PERMIT APPLICATION. | | | | | | E) I) AIPP COMPLIANCE REQUIRED; VERIFICATION REQUIRED | | | PRIOR TO C.O. | | | | | | CONTACT WITHIN 90 DAYS OF PERMIT ISSUANCE. | | | F) 5) CONSTRUCTION HOURS ? 7AM TO 7PM MON?FRI, 8AM TO | | | 8PM SAT?SUN | | | | | | | | | |
|