| Date |
Text |
| 2021-09-16 15:35:28 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 20030100 3111 S DIXIE HWY |
| | |
| | 2ND REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1. SECOND REQUEST: PLAN SHEET P-1.1 NOTES THAT WATER |
| | CONNECTIONS TO CM (CIVIL MAIN?). REFER TO CIVIL PLANS |
| | FOR LATERAL CONNECTION POINTS. PER WPB FBC 107.2.1, |
| | PROVIDE CIVIL DRAWINGS SHOWING THESE LATERAL CONNECTION |
| | POINTS. IF THE CIVIL DRAWINGS ARE UNDER A SEPARATE |
| | PERMIT, A COPY OF THE APPROPRIATE PAGE(S) MAY BE |
| | SUBMITTED AS REFERENCE ONLY. |
| | |
| | 2. NEW COMMENT: REGARDING ENGINEER?S RESPONSE THAT ALL |
| | DRAINAGE HAS BEEN REMOVED. PER WPB FBC 107.2.1, PROVIDE |
| | CLARIFICATION AS TO WHAT HAS CHANGED THAT AN OIL/WATER |
| | SEPARATOR IS NO LONGER REQUIRED. PROVIDE MANUFACTURER?S |
| | EQUIPMENT INSTALLATION AND RECOMMENDATIONS TO SUPPORT. |
| | |
| | 3. N/A |
| | |
| | 4. SECOND REQUEST: APPLICATION IS FOR TRASH ENCLOSURE |
| | #2. PLAN SHEETS SP-TRH AND TRH 1.1 REFERENCE TRASH |
| | ENCLOSURE #1. PER WPB FBC 107.2.1, CLARIFY AND |
| | RECONCILE. CLARIFY ON P-1.1 AND REMOVE REFERENCES TO |
| | WHICHEVER TRASH ENCLOSURE IS NOT PART OF THE PERMIT |
| | APPLICATION. |
| | I SEE NOTHING THAT INDICATES ON REVISED P1.1 V2 THAT |
| | IDENTIFIES TRASH ENCLOSURE #2 AS THE STRUCTURE BEING |
| | PERMITTED. THE TWO STRUCTURES SHOWN ARE NOT IDENTIFIED |
| | AS TRASH ENCLOSURE #1 AND TRASH ENCLOSURE #2. |
| | PER WPB FBC 107.2.1, |
| | ...A)IDENTIFY EACH OF THE TWO STRUCTURES |
| | ...B)PROVIDE A NOTE STATING TRASH ENCLOSURE #1 IS NOT |
| | IN THE SCOPE OF WORK. |
| | |
| | 5. NEW COMMENT: PER WPB FBC 107.2.1, PROVIDE DETAIL AND |
| | SPECIFICATION FOR RPZ. |
| | |
| | 6. NEW COMMENT: RE: P-2.0; ALL DRAINAGE APPEARS TO HAVE |
| | BEEN DELETED. PER WPB FBC 107.2.1, REMOVE ALL NOTES, |
| | SCHEDULES AND DETAILS THAT REFER TO SAID DRAINAGE. |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | ALL PLANS TO BE SIGNED AND SEALED BY THE DESIGNER AS |
| | REQUIRED BY FAC AND FS. |
| | ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE |
| | DESIGNER IN ACCORDANCE WITH FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-246-0882 MOBILE |
| | |
| | 20030100 3111 S DIXIE HWY |
| | |