Plan Review Notes
Plan Review Notes For Permit 20030100
Permit Number 20030100
Review Stop P
Sequence Number 2
Notes
Date Text
2021-09-16 15:35:28CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20030100 3111 S DIXIE HWY
  
 2ND REVIEW
 PLUMBING COMMENTS: DENIED
  
 1. SECOND REQUEST: PLAN SHEET P-1.1 NOTES THAT WATER
 CONNECTIONS TO CM (CIVIL MAIN?). REFER TO CIVIL PLANS
 FOR LATERAL CONNECTION POINTS. PER WPB FBC 107.2.1,
 PROVIDE CIVIL DRAWINGS SHOWING THESE LATERAL CONNECTION
 POINTS. IF THE CIVIL DRAWINGS ARE UNDER A SEPARATE
 PERMIT, A COPY OF THE APPROPRIATE PAGE(S) MAY BE
 SUBMITTED AS REFERENCE ONLY.
  
 2. NEW COMMENT: REGARDING ENGINEER?S RESPONSE THAT ALL
 DRAINAGE HAS BEEN REMOVED. PER WPB FBC 107.2.1, PROVIDE
 CLARIFICATION AS TO WHAT HAS CHANGED THAT AN OIL/WATER
 SEPARATOR IS NO LONGER REQUIRED. PROVIDE MANUFACTURER?S
 EQUIPMENT INSTALLATION AND RECOMMENDATIONS TO SUPPORT.
  
 3. N/A
  
 4. SECOND REQUEST: APPLICATION IS FOR TRASH ENCLOSURE
 #2. PLAN SHEETS SP-TRH AND TRH 1.1 REFERENCE TRASH
 ENCLOSURE #1. PER WPB FBC 107.2.1, CLARIFY AND
 RECONCILE. CLARIFY ON P-1.1 AND REMOVE REFERENCES TO
 WHICHEVER TRASH ENCLOSURE IS NOT PART OF THE PERMIT
 APPLICATION.
 I SEE NOTHING THAT INDICATES ON REVISED P1.1 V2 THAT
 IDENTIFIES TRASH ENCLOSURE #2 AS THE STRUCTURE BEING
 PERMITTED. THE TWO STRUCTURES SHOWN ARE NOT IDENTIFIED
 AS TRASH ENCLOSURE #1 AND TRASH ENCLOSURE #2.
 PER WPB FBC 107.2.1,
 ...A)IDENTIFY EACH OF THE TWO STRUCTURES
 ...B)PROVIDE A NOTE STATING TRASH ENCLOSURE #1 IS NOT
 IN THE SCOPE OF WORK.
  
 5. NEW COMMENT: PER WPB FBC 107.2.1, PROVIDE DETAIL AND
 SPECIFICATION FOR RPZ.
  
 6. NEW COMMENT: RE: P-2.0; ALL DRAINAGE APPEARS TO HAVE
 BEEN DELETED. PER WPB FBC 107.2.1, REMOVE ALL NOTES,
 SCHEDULES AND DETAILS THAT REFER TO SAID DRAINAGE.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE SIGNED AND SEALED BY THE DESIGNER AS
 REQUIRED BY FAC AND FS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
  
  