| Date |
Text |
| 2020-05-22 09:56:32 | REVIEWED BY JERRY SMITH. |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 20030100 3111 S DIXIE HWY |
| | |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | 1. PLAN SHEET P-1.1 NOTES THAT WATER CONNECTIONS TO CM |
| | (CIVIL MAIN?). REFER TO CIVIL PLANS FOR LATERAL |
| | CONNECTION POINTS. THE SAME NOTES ARE MADE CONCERNING |
| | SANITARY AND STORM. PER WPB FBC 107.2.1, PROVIDE CIVIL |
| | DRAWINGS SHOWING THESE LATERAL CONNECTION POINTS. |
| | PLEASE BE ADVISED THAT PER WPB CCCM, A BACKFLOW |
| | PREVENTER COMPLYING WITH THE REQUIREMENTS OF WPB CCCM |
| | AND FBC PL 608 IS REQUIRED ON A WATER SERVICE TO A |
| | STRUCTURE. PROVIDE THE SAME AS REQUIRED. |
| | 2. RE: PLAN SHEET P-1.1; PER WPB FBC 107.2.1, PROVIDE |
| | PLANS AND SPECIFICATION FOR DRAW OFF PIPING AND OIL |
| | STORAGE TANK IN CONJUNCTION WITH THE OIL INTERCEPTOR. |
| | THE PIPING AND CONNECTION INDICATED AS A VENT ON THE |
| | PLANS IS INCORRECT. THE CONNECTION IS FOR OIL DRAW OFF, |
| | NOT FOR VENTING. SEE MANUFACTURER?S SPECIFICATION |
| | INDICATED ON P-2.0. |
| | 3. RE: PLAN SHEET P-1.1; PER WPB FBC 107.2.1, SHOW TRAP |
| | PRIMER VALVE INSTALLATION IN THE WATER RISER AND PLAN |
| | VIEW. |
| | 4. APPLICATION IS FOR TRASH ENCLOSURE #2. PLAN SHEETS |
| | SP-TRH AND TRH 1.1 REFERENCE TRASH ENCLOSURE #1. PER |
| | WPB FBC 107.2.1, CLARIFY AND RECONCILE. CLARIFY ON |
| | P-1.1 AND REMOVE REFERENCES TO WHICHEVER TRASH |
| | ENCLOSURE IS NOT PART OF THE PERMIT APPLICATION. |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | ALL PLANS TO BE SIGNED AND SEALED BY THE DESIGNER AS |
| | REQUIRED BY FAC AND FS. |
| | ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE |
| | DESIGNER IN ACCORDANCE WITH FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-246-0882 MOBILE |
| | |
| | 20030100 3111 S DIXIE HWY |
| | |
| | |
| | |