Plan Review Notes
Plan Review Notes For Permit 20030098
Permit Number 20030098
Review Stop P
Sequence Number 3
Notes
Date Text
2020-09-14 14:06:293RD REVIEW FBC-2017 PLUMBING
 PERMIT- 20030098
 9/14/2020
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE COD1
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 COMMENTS #4, & 6 COPIED BELOW FROM THE PREVIOUS REVIEW
 WERE NOT ADDRESSED- PLEASE COMPLY.
  
 4) P2.0 & P2.1: SUBMIT MANUFACTURER'S SPECIFICATIONS
 IWH. THE SPECS MUST INDICATE THE UNIT IS RATED FOR
 OUTDOOR INSTALLATIONS- SECTION 502.1 FBC P.
  
 6)P2.1: NOTES ON THE WATER SUPPLY AND SANITARY DRAIN
 REFER TO CIVIL PLANS FOR POINTS OF CONNECTIONS. PLEASE
 PROVIDE THE PLANS- SECTION 107.2.1 WPB.
  
 NEW COMMENTS.
  
 1) THE REVISED P2.1 SHEET IS NOW SHOWING TWO NEW 4'
 UNDERGROUND SANITARY LINES AT THE PAVILION THAT ARE NOT
 LISTED "FOR REFERENCE ONLY" (PLEASE NOTE NEW WATER
 LINES AND BACKFLOW PREVENTERS TO THE POOLS ARE
 INDICATED FOR REFERENCE ONLY). PLEASE CLARIFY IF THE
 SANITARY LINES ARE TO BE INCLUDED IN THE SCOPE OF THE
 WORK UNDER THIS PERMIT, OR ARE FOR REFERENCE ONLY AND
 TO BE INCLUDED IN THE POOL OR CIVIL PLANS. PLEASE NOTE
 REQUIRED CLEANOUTS ARE NOT SHOWN, AND THERE HAS BEEN NO
 INCREASE IN THE VALUE OF THE POOL PAVILION PERMIT BASED
 ON THE ADDITIONAL WORK.
  
 2) P2.1: REFER TO SECTIONS 701.5 AND 1101.3 AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS FOR THE OUTDOOR SINK
 COVER. PROVIDE A DETAIL ON THE PLAN SHOWING HOW IT WILL
 BE SECURED TO THE SINK TO RESIST WIND PRESSURES FROM
 REMOVING IT- SECTION 107.2.1 WPB.
  
 3) P2.0: PLEASE PROVIDE A PLUMBING FIXTURE SCHEDULE ON
 THE PLAN- MAKE AND MODEL NUMBERS OF THE SK-1 AND THE
 FAUCET- SECTION 401.1 AND 404.1 FBC P. THE CONNECTION
 SCHEDULE REFERS TO ARCHITECTURAL PLANS WHICH DO NOT
 PROVIDE THE INFORMATION.
  
 4) PAV-3.1: PLEASE INDICATE THE LOCATION OF THE SINK
 FAUCET SHALL NOT EXCEED 24" FROM THE FRONT EDGE OF THE
 COUNTER AS REQUIRED BY SECTION 308.3.2 FBC ACC-
 OBSTRUCTED HIGH REACH FOR PARALLEL APPROACH.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  
  