| 2020-06-15 11:09:15 | 2ND REVIEW FBC-2017 FUEL GAS |
| | PERMIT- 20030098 |
| | 6/15/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P2.1: LOCATION OF NEW GAS METER NOT SHOWN- |
| | NOTES REFER TO CIVIL PLANSAND PIPING BY OTHERS. THE |
| | ACTUAL LOCATIONOF THE METER SND THE SCOPE OF WORK BY |
| | OTHERS ARE REQUIRED TO APPROVE THE GAS PLAN AND |
| | ISOMETRIC DRAWING- SECTION 107.2.1 WPB. |
| | |
| | 2) P2.0: AS PREVIOUSLY REQUESTED SUBMIT SPECS FOR THE |
| | BBQ?S. THE NOTE IN THE SCHEDULE REFERENCES THE |
| | ARCHITECTURAL PLANS WHICH DO NOT PROVIDE INFORMATION- |
| | SECTION 107.2.1 WPB. |
| | |
| | 3) SHEETS PAV-3.1: REFERENCES ARE MADE TO LANDSCAPE |
| | PLANS FOR THE GAS BBQ'S. THE PLANS SHEETS ARE NOT |
| | PROVIDED. PLEASE NOTE THAT DETAIL B APPEARS TO SHOW A |
| | WOOD FRAME SUPPORT WALL FOR THE BBQ WHICH IS |
| | COMBUSTIBLE CONSTRUCTION- SECTION 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |