2020-06-18 15:08:243RD REVIEW FBC-2017 PLUMBING
 PERMIT #20030076
 6/18//2020
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P1: THE MODEL NUMBER OF THE WATER HEATER SHOWN
 IN THE EQUIPMENT SCHEDULE DOES NOT MATCH ANY OF THE
 MODEL NUMBERS SHOWN IN THE WATER HEATER SPECS. A) THE
 90% (.90) EFF IS UNDER THE MINIMUM (.9172) REQUIRED
 PERFORMANCE PER TABLE C404.2 FBC EC. PLEASE SEE THE
 EQUATION FOR ELECTRIC WATER HEATERS LESS THAN 12 KW.
  
 2) SHEETS A101 & P3: PLACE CLEAR FLOOR SPACE DIAGRAMS
 AND DIMENSIONS TO CLARIFY THE LOCATIONS OF ALL
 ACCESSIBLE EXAM, MEDICAL, AND LAB SINKS- SECTION 212.3
 AND 606.1 FBC ACC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER