| 2020-05-12 12:48:29 | 2ND REVIEW FBC-2017 PLUMBING |
| | PERMIT #20030076 |
| | 5/12/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P6: THE REQUESTED LEGEND FOR THE NUMBERED |
| | NOTES AT THE WATER HEATER DETAIL WAS NOT PROVIDED- |
| | SECTION 107.2.1 WPB. |
| | |
| | 2) P6: WATER HEATER PAN DRAIN PIPE AND TERMINATION |
| | LOCATION NOT SHOWN- SECTIONS 504.7.1 & 504.7.2 FBC P. |
| | |
| | 3) P1: PLEASE INCLUDE THE EFFICIENCY RATING OF THE |
| | WATER HEATER IN THE EQUIPMENT SCHEDULE AND SUBMIT A CUT |
| | SHEET TO VERIFY THE COMPLIANCE DATA NOTED IN THE |
| | ENERGYGAUGE SUBMITTAL- TABLE C404.2 FBC EC. |
| | |
| | 4) P3 & P5: A) SHOW THE REFRIGERATOR ICE MAKE LINE |
| | CONNECTION AND REQUIRED WATER HAMMER ARRESTOR- SECTION |
| | 604.9 FBC P. B) SHOW THE REQUIRED WATER HAMMER ARRESTOR |
| | FOR THE EWC1- SECTION 604.9. C) SHOW THE REQUIRED |
| | BACKFLOW PREVENTERS AND CONNECTION LOCATIONS TO THE ICE |
| | MAKER LINE, THE COFFEE MAKER, AND ALL OTHER DEVICES, |
| | APPLIANCES, APPURTENANCES, APPARATUS USED FOR SOME |
| | SPECIAL FUNCTION SUCH AS STERILIZATION OR PROCESSING- |
| | SECTIONS 608.3 & 608.16.10 FBC P. |
| | |
| | 5) P1: PROVIDE EQUIPMENT SCHEDULES FOR THE BACKFLOW |
| | PREVENTERS- TABLE 608.1 FBC P. |
| | |
| | 6) P1, P3, & P5: SHOW THE MIXING VALVE LOCATIONS FOR |
| | THE PUBLIC LAVATORIES- SECTION 416.5 FBC P. INDICATE |
| | THE VALVE IS ASSE 1070 COMPLIANT- SECTION 607.1.2 FBC |
| | P. |
| | |
| | 7) MISSING ACCESSIBILITY DETAILS: |
| | A) DRINKING FOUNTAIN CLEAR FLOOR SPACE APPROACH, KNEE |
| | AND TOE CLEARANCES, SPOUT HEIGHTS ETC- SECTION 602.1 |
| | FBC ACC. |
| | B) LOUNGE AND WAITING ROOM SINK CLEAR FLOOR SPACE |
| | APPROACHES, WAITING ROOM SINK RIM OR COUNTER HEIGHT, |
| | AND KNEE AND TOE CLEARANCES- SECTION 606.1 FBC ACC. |
| | C) DESIGNATED ACCESSIBLE EXAM ROOM SINK IDENTIFIED, |
| | CLEAR FLOOR SPACE APPROACH, SINK RIM OR COUNTER HEIGHT, |
| | KNEE AND TOE CLEARANCES- SECTIONS 212.3 & 606.1 FBC |
| | ACC. |
| | D) MEDICAL ROOM AND LAB ROOM SINK CLEAR FLOOR SPACE |
| | APPROACHES, SINK RIM OR COUNTER HEIGHTS, KNEE AND TOE |
| | CLEARANCES- SECTIONS 212.3 & 606.1 FBC ACC. |
| | |
| | 8) A-101 & A-401: TOILET ROOM 232 OR 119- WHICH IS IT? |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |