Plan Review Notes
Plan Review Notes For Permit 20030076
Permit Number 20030076
Review Stop P
Sequence Number 2
Notes
Date Text
2020-05-12 12:48:292ND REVIEW FBC-2017 PLUMBING
 PERMIT #20030076
 5/12/2020
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P6: THE REQUESTED LEGEND FOR THE NUMBERED
 NOTES AT THE WATER HEATER DETAIL WAS NOT PROVIDED-
 SECTION 107.2.1 WPB.
  
 2) P6: WATER HEATER PAN DRAIN PIPE AND TERMINATION
 LOCATION NOT SHOWN- SECTIONS 504.7.1 & 504.7.2 FBC P.
  
 3) P1: PLEASE INCLUDE THE EFFICIENCY RATING OF THE
 WATER HEATER IN THE EQUIPMENT SCHEDULE AND SUBMIT A CUT
 SHEET TO VERIFY THE COMPLIANCE DATA NOTED IN THE
 ENERGYGAUGE SUBMITTAL- TABLE C404.2 FBC EC.
  
 4) P3 & P5: A) SHOW THE REFRIGERATOR ICE MAKE LINE
 CONNECTION AND REQUIRED WATER HAMMER ARRESTOR- SECTION
 604.9 FBC P. B) SHOW THE REQUIRED WATER HAMMER ARRESTOR
 FOR THE EWC1- SECTION 604.9. C) SHOW THE REQUIRED
 BACKFLOW PREVENTERS AND CONNECTION LOCATIONS TO THE ICE
 MAKER LINE, THE COFFEE MAKER, AND ALL OTHER DEVICES,
 APPLIANCES, APPURTENANCES, APPARATUS USED FOR SOME
 SPECIAL FUNCTION SUCH AS STERILIZATION OR PROCESSING-
 SECTIONS 608.3 & 608.16.10 FBC P.
  
 5) P1: PROVIDE EQUIPMENT SCHEDULES FOR THE BACKFLOW
 PREVENTERS- TABLE 608.1 FBC P.
  
 6) P1, P3, & P5: SHOW THE MIXING VALVE LOCATIONS FOR
 THE PUBLIC LAVATORIES- SECTION 416.5 FBC P. INDICATE
 THE VALVE IS ASSE 1070 COMPLIANT- SECTION 607.1.2 FBC
 P.
  
 7) MISSING ACCESSIBILITY DETAILS:
 A) DRINKING FOUNTAIN CLEAR FLOOR SPACE APPROACH, KNEE
 AND TOE CLEARANCES, SPOUT HEIGHTS ETC- SECTION 602.1
 FBC ACC.
 B) LOUNGE AND WAITING ROOM SINK CLEAR FLOOR SPACE
 APPROACHES, WAITING ROOM SINK RIM OR COUNTER HEIGHT,
 AND KNEE AND TOE CLEARANCES- SECTION 606.1 FBC ACC.
 C) DESIGNATED ACCESSIBLE EXAM ROOM SINK IDENTIFIED,
 CLEAR FLOOR SPACE APPROACH, SINK RIM OR COUNTER HEIGHT,
 KNEE AND TOE CLEARANCES- SECTIONS 212.3 & 606.1 FBC
 ACC.
 D) MEDICAL ROOM AND LAB ROOM SINK CLEAR FLOOR SPACE
 APPROACHES, SINK RIM OR COUNTER HEIGHTS, KNEE AND TOE
 CLEARANCES- SECTIONS 212.3 & 606.1 FBC ACC.
  
 8) A-101 & A-401: TOILET ROOM 232 OR 119- WHICH IS IT?
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  