| Plan Review Notes For Permit 20030076 |
| Permit Number |
20030076 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-03-27 09:12:42 | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | FBC P = FBC PLUMBING | | | | | | 1. 2017 FBC ENERGY CODE. PROVIDE ENERGY CALCULATIONS | | | AND HEATING/COOLING LOAD CALCULATIONS AS REQUIRED. | | | 2. 2017 FBC WIND LOADING. FOR ALL ROOF TOP MOUNTED | | | EQUIPMENT, CURBS, PIPING AND PIPE STANDS, ETC. PROVIDE | | | EITHER NOA OR FLORIDA APPROVED DETAILS WITH APPROVAL | | | NUMBERS OR SIGNED AND SEALED STRUCTURAL DOCUMENTS WITH | | | CALCULATIONS FOR WITHSTANDING WIND LOADING FOR WEST | | | PALM BEACH AREA. | | | 3. 2017 FBC 107.2.1 PROVIDE REFRIGERANT PIPING SIZING | | | ON DRAWINGS. | | | PLEASE PROVIDE COMMENT/RESPONSE LETTER WITH RESUBMITTAL | | | FOR EXPEDITIOUS REVIEW. | | | | | | REVIEWED REMOTELY BY JAMES BAKER, PE | | | PX3997, PE77268 | | | 561-805-6724 | | | [email protected] | | | | | | |
|