2020-04-08 10:00:37CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE AND DOWNSTREAM PANEL INCLUDING INFORMATION FROM
 THE POWER COMPANY STATING WHAT THE AVAILABLE SHORT
 CIRCUIT CURRENT IS FOR THE SERVICE TO CONFIRM THE
 STATED AIC RATING OF THE SERVICE EQUIPMENT AND PANELS
 IS ADEQUATE. NEC 110.9, 110.10
 2. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 3. PROVIDE AIC RATING OF ANY SERVICE DISCONNECTS AND
 PANELS. NEC 110.3, 110.9
 4. PROVIDE THE ADDITIONAL INTERIOR LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. MANY AREAS DO NOT
 SHOW THE AUTOMATIC CONTROL REQUIRED. WHILE A DETAIL WAS
 PROVIDED FOR LIGHTING CONTROLS, THE LIGHTING PLAN DOES
 NOT SHOW IMPLEMENTATION. FBC EC C405.2; WPB FBC 107.2.1
 5. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2
 6. PLEASE INDICATE ON PLANS WHICH ROOMS SHALL BE WIRED
 PER NEC 517.13. WHAT TYPE OF HEALTH CARE FACILITY IS
 THIS? PROVIDE DETAILS. WPB FBC 107.2.1; NEC 517.13
 7. IS THERE ANY TYPE OF ESSENTIAL ELECTRICAL SYSTEM
 REQUIRED FOR THIS FACILITY? THE PLAN PROVIDED IS
 LACKING INFORMATION. PROVIDE DETAILS. NEC 517.25,517.40
 8. IS THERE ANY TYPE OF PEDIATRIC CARE AT THIS FACILITY
 THAT WOULD REQUIRE TAMPER-RESISTANT RECEPTACLES? THE
 PLAN PROVIDED IS LACKING INFORMATION. PROVIDE DETAILS.
 NEC 517.18(C)
 9. FIRE ALARM, LOW VOLTAGE SYSTEMS, DAS, LIGHTNING
 PROTECTION, GENERATORS, COMMERCIAL HOOD SYSTEMS, WALK
 IN COOLERS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND PLAN SUBMITTALS FOR ANY
 OF THESE SYSTEMS PRESENT. WPB FBC 105.1, 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746