| 2020-04-08 10:00:37 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR |
| | SERVICE AND DOWNSTREAM PANEL INCLUDING INFORMATION FROM |
| | THE POWER COMPANY STATING WHAT THE AVAILABLE SHORT |
| | CIRCUIT CURRENT IS FOR THE SERVICE TO CONFIRM THE |
| | STATED AIC RATING OF THE SERVICE EQUIPMENT AND PANELS |
| | IS ADEQUATE. NEC 110.9, 110.10 |
| | 2. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF |
| | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND |
| | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 |
| | 3. PROVIDE AIC RATING OF ANY SERVICE DISCONNECTS AND |
| | PANELS. NEC 110.3, 110.9 |
| | 4. PROVIDE THE ADDITIONAL INTERIOR LIGHTING CONTROLS |
| | STIPULATED IN THE FBC ENERGY CODE. MANY AREAS DO NOT |
| | SHOW THE AUTOMATIC CONTROL REQUIRED. WHILE A DETAIL WAS |
| | PROVIDED FOR LIGHTING CONTROLS, THE LIGHTING PLAN DOES |
| | NOT SHOW IMPLEMENTATION. FBC EC C405.2; WPB FBC 107.2.1 |
| | 5. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES |
| | EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN |
| | RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR |
| | LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2 |
| | 6. PLEASE INDICATE ON PLANS WHICH ROOMS SHALL BE WIRED |
| | PER NEC 517.13. WHAT TYPE OF HEALTH CARE FACILITY IS |
| | THIS? PROVIDE DETAILS. WPB FBC 107.2.1; NEC 517.13 |
| | 7. IS THERE ANY TYPE OF ESSENTIAL ELECTRICAL SYSTEM |
| | REQUIRED FOR THIS FACILITY? THE PLAN PROVIDED IS |
| | LACKING INFORMATION. PROVIDE DETAILS. NEC 517.25,517.40 |
| | 8. IS THERE ANY TYPE OF PEDIATRIC CARE AT THIS FACILITY |
| | THAT WOULD REQUIRE TAMPER-RESISTANT RECEPTACLES? THE |
| | PLAN PROVIDED IS LACKING INFORMATION. PROVIDE DETAILS. |
| | NEC 517.18(C) |
| | 9. FIRE ALARM, LOW VOLTAGE SYSTEMS, DAS, LIGHTNING |
| | PROTECTION, GENERATORS, COMMERCIAL HOOD SYSTEMS, WALK |
| | IN COOLERS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS |
| | (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF |
| | THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE |
| | REQUIRED SEPARATE PERMITS AND PLAN SUBMITTALS FOR ANY |
| | OF THESE SYSTEMS PRESENT. WPB FBC 105.1, 107.2.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. |
| | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL |
| | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |