Notes
Date Text
2020-03-19 17:09:3003/23/2020 REVISED COMMENT #1. TALKED TO ROSANA CASAS
 (ARCH.) MULTIPURPOSE ROOM IS TO BE USED BY RESIDENTS
 AND THEIR GUESTS ONLY. NOT FOR THE PUBLIC. KITCHENETTE
 TO COMPLY WITH THE FAIR HOUSING ACT GUIDELINES. SEE
 REVISED COMMENT BELOW.
 1- A NEW KITCHENETTE IS SHOWN ON THE REVISED
 MULTIPURPOSE ROOM. THE MICROWAVE SHOWN ON THE INTERIOR
 ELEVATION ON SHEET A3.13 DOESN'T COMPLY WITH THE THE
 PARALLEL OR PERPENDICULAR CLEAR FLOOR SPACE AS REQUIRED
 BY FAIR HOUSING ACT GUIDELINES.
  
  
 REVISION, BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- A NEW KITCHENETTE IS SHOWN ON THE REVISED
 MULTIPURPOSE ROOM. THE MICROWAVE SHOWN ON THE INTERIOR
 ELEVATION ON SHEET A3.13 DOESN'T COMPLY WITH THE REACH
 RANGE REQUIRED BY SEC. 308 FBC-ACCESSIBILITY. REVISE AS
 REQUIRED SHOWING COMPLIANCE.
 SEC. 212 AND SEC. 804 FBC-ACCESSIBILITY.
  
 2- NEW MULTIPURPOSE ROOM IS BIGGER THAN THE ONE ON THE
 APPROVED PLANS. REVISE LIFE-SAFETY PLAN SHOWING THE NEW
 OCCUPANT LOAD. SEC. 1004.1.2 FBC-BUILDING.
  
  
 WHEN RESUBMITTING A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
 03/23/2020 REVISED COMMENT #1. TALKED TO ROSANA CASAS
 (ARCH.) MULTIPURPOSE ROOM IS TO BE USED BY RESIDENTS
 AND THEIR GUESTS ONLY. KITCHENETTE TO OMPLY WITH-THE
 FAIR HOUSING ACT GUIDELINES. SEE REVISED COMMENT BELOW.
 1- A NEW KITCHENETTE IS SHOWN ON THE REVISED
 MULTIPURPOSE ROOM. THE MICROWAVE SHOWN ON THE INTERIOR
 ELEVATION ON SHEET A3.13 DOESN'T COMPLY WITH THE
 GUIDELINES FOR KITCHENS. SEE PAGE 2.14 AND PAGE 7.6 OF
 FAIR HOUSING ACT DESIGN MANUAL. REVISE PLANS AS
 REQUIRED SHOWING COMPLIANCE.