| Date |
Text |
| 2020-03-10 09:12:40 | 1) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE |
| | FIREPLACE, THE COOKTOP AND THE DRYER. 2017 FBC-FUEL GAS |
| | CODE SEC.304.1, 614.6 (CLOTHES DRYERS) OR 2017 FBC-RES. |
| | SEC.G 2407.1 AND G2439.4 (CLOTHES DRYERS). 2ND REQUEST. |
| | 2) THE GAS ISOMETRIC LEGEND LISTS CSST GAS PIPING. IS |
| | THIS PIPING MATERIAL GOING TO BE INSTALLED? IF SO, |
| | SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLE USED |
| | TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE |
| | PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE FROM THE |
| | GAS CODE OR OTHER STANDARD THAT WAS USED IN THE DESIGN |
| | OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL GAS |
| | SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1) THRU |
| | 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8, |
| | G2413.1, G2413.2, & G2413.3. 2ND REQUEST. |
| | 3) SUBMIT TWO COPIES OF THE MANUFACTURER'S |
| | SPECIFICATIONS AND INSTALLATION INSTRUCTIONS FOR THE |
| | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION. THE SUBMITTED SHEETS FOR THE 325-L SERIES |
| | GAS REGULATOR DO NOT STATE THAT THE REGULATOR IS |
| | APPROVED FOR OUTDOOR USE. 2ND REQUEST. |
| | 4) WHERE CONNECTED TO RIGID PIPING, A UNION SHALL BE |
| | INSTALLED WITHIN ONE (1) FOOT OF EITHER SIDE OF THE MP |
| | REGULATOR. 2017 FBC-RESIDENTIAL SEC. G2421.2 (7), 2017 |
| | FBC-FUEL GAS SEC. 410.2 (7). 2ND REQUEST. |
| | 5) SHOW THE CORRESPONDING EHD (EQUIVALENT HYDRAULIC |
| | DIAMETER) FOR THE CSST IF BEING INSTALLED. SEE FOOTNOTE |
| | AT BOTTOM OF CSST SIZING TABLES IN THE FUEL GAS |
| | CODE.2ND REQUEST. |
| | 6) SUBMIT TWO COPIES OF THE INSTALLATION MANUAL FOR THE |
| | CSST PIPING IF IT IS TO BE INSTALLED OR COMPLY WITH THE |
| | SIZING TABLES IN THE 2017 FBC-FUEL GAS CODE. 2017 |
| | FBC-FUEL GAS SEC. 404.1.2ND REQUEST. |
| | NOTE: DO NOT RESUBMIT THESE PLANS UNTIL ALL OF THE |
| | ABOVE COMMENTS HAVE BEEN ADDRESSED. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |