2020-03-02 06:44:111) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE
 FIREPLACE, THE COOKTOP AND THE DRYER THE 2017 FBC-FUEL
 GAS CODE SEC.304.1, 614.6 (CLOTHES DRYERS) OR 2017
 FBC-RES. SEC.G 2407.1 AND G2439.4 (CLOTHES DRYERS).
 2) THE GAS ISOMETRIC LEGEND LISTS CSST GAS PIPING. IS
 THIS PIPING MATERIAL GOING TO BE INSTALLED? IF SO,
 SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLE USED
 TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE FROM THE
 GAS CODE OR OTHER STANDARD THAT WAS USED IN THE DESIGN
 OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL GAS
 SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1) THRU
 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8,
 G2413.1, G2413.2, & G2413.3.
 4) A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR. 2017 FBC-FUEL
 GAS SEC.409.4, FBC-RESIDENTIAL SEC. G 2420.4.
 5) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE PRESSURE REGULATORS.
 REGULATORS INSTALLED ON THE EXTERIOR OF THE BUILDING
 SHALL BE APPROVED FOR OUTDOOR INSTALLATION. IDENTIFY ON
 THE SPECIFICATION SHEETS WHICH MODEL REGULATOR IS BEING
 INSTALLED AND THE ORIFICE SIZE TO ENSURE THE REGULATOR
 CAN ACCOMMODATE THE BTU LOAD THROUGH THE REGULATOR.2017
 FGC SEC.410.1, 2017 FBC-RES. SEC. G2421.1.
 6) WHERE CONNECTED TO RIGID PIPING, A UNION SHALL BE
 INSTALLED WITHIN ONE (1) FOOT OF EITHER SIDE OF THE MP
 REGULATOR. 2017 FBC-RESIDENTIAL SEC. G2421.2 (7), 2017
 FBC-FUEL GAS SEC. 410.2 (7).
 7) IF THE GAS SYSTEM PRESSURE IS 12 INCHES OF WATER
 COLUMN, A REGULATOR MAY BE REQUIRED AT THE TANKLESS
 WATER HEATER. REFER TO THE MANUFACTURER'S INSTALLATION
 MANUAL . 2017 FBC-FUEL GAS SEC.305.1.
 8) SHOW THE CORRESPONDING EHD (EQUIVALENT HYDRAULIC
 DIAMETER) FOR THE CSST IF BEING INSTALLED. SEE FOOTNOTE
 AT BOTTOM OF CSST SIZING TABLES IN THE FUEL GAS CODE.
 9) SUBMIT TWO COPIES OF THE INSTALLATION MANUAL FOR THE
 CSST PIPING IF IT IS TO BE INSTALLED. 2017 FBC-FUEL GAS
 SEC. 404.1.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW