| 2020-04-24 15:59:18 | PLAN REVIEW - ELECTRICAL |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER ? BUILDING - PX3169 |
| | PLANS EXAMINER ? 1&2 FAMILY - SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 2ND REVIEW |
| | |
| | RESULTS: DENIED |
| | |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. |
| | PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED |
| | SATISFACTORILY HAVE ADDITIONAL COMMENTS IN PARENTHESES. |
| | ANY NEW COMMENT WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | JAKE LEAHY |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | 1) PAGE A.04 |
| | |
| | PANEL "G" WILL REQUIRE A GROUNDING ELECTRODE SYSTEM TO |
| | BE INSTALLED 250.32(A) - CORRECTED |
| | |
| | MDP 400A PANEL WILL NEED A LOAD CALCULATION FOR THE |
| | ADDED LOAD FROM PANEL "G" (NOT ADDRESSED) |
| | |
| | NEW COMMENTS: |
| | |
| | 2) THE FUTURE PANEL "G" 60A ON THE RISER DIAGRAHM IS |
| | NOT LABLED. THE NEW PANEL SCHEDULE AND LOAD CALC'S FOR |
| | THE PROPOSED GARAGE IS LABLED PANEL "F". |
| | PLEASE CLARIFY. |
| | |
| | 3) THE PANEL SCHEDULE TO THE LEFT OF THE NEW GARAGE |
| | PANEL IS NOT LABLED. IS THIS THE MDP 400A PANEL? ALL |
| | CIRCUTS ARE LABLED CIR# 1 EXCEPT FOR 2 LABLED #2. |
| | PLEASE LABLE CIRCUTS CORRECTLY. |
| | |
| | 4) THE UNLABLED PANEL SCHEDULE SHOWS THE CAR CHARGER |
| | CIRCUT WITH A 2 POLE 50A OCP WITH 12000 WATTS. THE NEW |
| | GARAGE PANEL SHOWS THE CAR CHARGER CIRCUT WITH A 2 POLE |
| | 50A OCP WITH 24000 WATTS. |
| | PLEASE CLARIFY. |
| | |
| | 5) THE UNLABLED SCHEDULE SHOWS THE GARAGE DOOR OPENER |
| | WITH A 20A OCP. THE NEW GARAGE SCHEDULE SHOWS THE |
| | GARAGE DOOR OPENER WITH A 15A OCP. |
| | PLEASE CLARIFY. |
| | |
| | |
| | |
| | |
| | |