| Plan Review Notes For Permit 20021265 |
| Permit Number |
20021265 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-03-23 13:26:29 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) PAGE A.04 | | | | | | PANEL "G" WILL REQUIRE A GROUNDING ELECTRODE SYSTEM TO | | | BE INSTALLED 250.32(A) | | | | | | MDP 400A PANEL WILL NEED A LOAD CALCULATION FOR THE | | | ADDED LOAD FROM PANEL "G" | | | | | | | | 2020-03-22 09:34:12 | JL |
|