| Plan Review Notes For Permit 20021260 |
| Permit Number |
20021260 |
|
| Review Stop |
ENG |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-03-05 07:36:23 | THE DCDA CALLED OUT ON THE SUBMITTED DRAWINGS (4 IN. | | | AMES 3000SS DCDA) DOES NOT MATCH THE BACKFLOW SHOWN ON | | | THE APPROVED CONSTRUCTION PLANS AND APPROVED MATERIAL | | | LIST FOR THE PBAU RESIDENTIAL DORMATORY PROJECT | | | E19020002. | | | | | | BOTH THE APPROVED CONSTRUCTION PLANS AND APPROVED | | | MATERIAL LIST SHOW A 6 IN. DCDA. THE APPROVED MATERIALS | | | LIST SPECIFIES A ZURN-WILKINS 6 IN. DCDA (350 ASTDA | | | MODEL) BACKFLOW. | | | | | | FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR | | | CONCERNS, THANKS. | | | | | | RICK ROSSANO, PROJECT COORDINATOR | | | ENGINEERING SERVICES DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 (MAILING ADDRESS: P.O. BOX | | | 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 DIRECT: (561) 494-1098 FAX: | | | (561) 494-1116 MOBILE: (561) 246-9525 | | | EMAIL: [email protected] WWW.WPB.ORG/ENGINEERING | | | |
|