Plan Review Notes
Plan Review Notes For Permit 20021256
Permit Number 20021256
Review Stop P
Sequence Number 1
Notes
Date Text
2020-03-20 16:57:241ST REVIEW FBC-2017 PLUMBING
 PERMIT #20021256
 3/20/20
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTHE EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE A FOOD SERVICE EQUIPMENT PLAN AND
 EQUIPMENT SCHEDULE- SECTION 107.2.1 WPB.
  
 2) SHEETS A.0, A4.0 & P2.2: THE PLANS SHALL BE DESIGNED
 IN ACCORDANCE WITH THE FLORIDA ACCESSIBILITY SIXTH
 EDITION 2017 CODE. PLEASE REMOVE REFERENCES TO ADA.
  
 3) A4.0, DETAIL C: PROVIDE THE HEIGHT OF THE SIDE WALL
 GRAB BAR FROM THE FINISHED FLOOR- SECTION 609.4 FBC
 ACC. A) SHOW THE REQUIRED 54" MINIMUM EXTENSION OF THE
 SIDE WALL GRAB BAR FROM THE REAR WALL- SECTION 604.5.1
 FBC ACC.
  
 4) A2.0 & A4.0: SHOW THE REQUIRED CLEAR FLOOR SPACE AND
 KNEE AND TOE CLEARANCE FOR THE ACCESSIBLE DRINKING
 FOUNTAIN- SEE SECTIONS 305, 306, & 602.2 FBC ACC.
  
 5) A2.0, A4.0 & P2.2: THE BREAKROOM SINK IS NOT SHOWN
 ON ANY OF THE ARCHITECTURAL OF PLUMBING DRAWINGS APART
 FROM P2.2. PLEASE NOTE THE SINK SHALL BE ACCESSIBLE AND
 MEET ALL REQUIREMENTS LISTED UNDER SECTIONS 606.2
 THROUGH 606.5 FBC ACC.
  
 6) A2.0, A4.0, P1.1 & P2.2: PLEASE SHOW THE
 WASHER/DRYER CONSISTENTLY ON ALL THE DRAWINGS AND REFER
 TO SECTION 611 FBC ACC OR ACCESSIBILITY REQUIREMENTS.
  
 6) P0.1: BECAUSE ALL PLUMBING FIXTURES ARE REQUIRED TO
 MEET THE CURRENT ASME AND NSF STANDARDS, "BY OWNER" IS
 NOT AN ACCEPTABLE ALTERNATIVE FROM PROVIDING
 MANUFACTURER AND MODEL NUMBERS OF THE 3-COMPARTMENT AND
 DEEP SINKS, AND THE TRENCH DRAINS- SECTIONS 418.1 &
 412.1 FBC P. A) PLEASE ADD THE FLOOR SINKS AND HUB
 DRAINS TO THE SCHEDULE-
  
 7) P0.1 & P1.1: A SEPARATE PERMIT IS REQUIRED FOR THE
 GREASE INTERCEPTOR, HOWEVER BASED ON THE CURRENT PLANS,
 A THOROUGH REVIEW CANNOT BE COMPLETED. PLEASE NOTE:
 A) THE GREASE INTERCEPTOR SIZING CALCULATIONS DO NOT
 INCLUDE THE VARIOUS FLOOR AND TROUGH DRAINS SHOWN ON
 THE PLANS. BECAUSE THERE ARE NO FOOD SERVICE PLANS IT
 IS NOT CLEAR IF THOSE FIXTURES NEED TO BE INCLUDED IN
 THE CALCULATIONS- SECTION 1003.1 FBC P.
 B) REFER TO SECTIONS 1000.3.4 THROUGH 1003.3.6 FBC P:
 MANUFACTURER'S SPECIFICATIONS MUST BE SUBMITTED WITH
 APPROVAL STAMP BY THE ENGINEER OF RECORD.
 C) CIVIL PLANS MUST BE SUBMITTED SHOWING THE LOCATION
 OF THE UNDERGROUND INTERCEPTOR AND THE INLET AND
 CONNECTION OF THE GREASE WASTE LINE AND THE DISCHARGE
 PIPING CONNECTION INTO THE MAIN SANITARY SEWER. PLEASE
 NOTE THAT HYDRO MECHANICAL TYPE INTERCEPTORS REQUIRE
 VENTED FLOW CONTROL DEVICES AND ALL INTERCEPTORS
 REQUIRE APPROVAL BY THE WPB UTILITIES DEPARTMENT. FOR
 FURTHER INFORMATION PLEASE CONTACT CHIEF PLUMBING
 INSPECTOR TIMOTHY LARGE- 561-805-6692.
  
 8) P0.1 & P2.2 WATER HEATER: A) SUBMIT MANUFACTURER'S
 SPECIFICATIONS WITH APPROVAL STAMP BY THE EOR- SECTION
 502.1 FBC P. B) REFER TO SECTION 502.5 AND INDICATE HOW
 THE WATER HEATER WILL BE SUPPORTED ABOVE THE CEILING
 AND HOW ACCESS WILL BE PROVIDED. PLEASE NOTE THAT A
 30X30" LEVEL WORKING SPACE SHALL BE PROVIDED IN FRONT
 OF THE CONTROL SIDE OF THE APPLIANCE. C) PROVIDE THE
 CORRECT CODE SECTIONS SHOWN IN THE WATER PIPING DETAIL-
 SECTIONS 504.7 THROUGH 504.7.2 FBC P. D) THE 0.93
 ENERGY FACTOR IN THE SCHEDULE DOES NOT MATCH THE 0.92
 FACTOR IN THE ENERGYGAUGE COMPLIANCE REPORT- SEE TABLE
 C404.2 FBC EC- NOTE THE 0.90 MIN. EFF REQUIRED IS NOT
 IN COMPLIANCE WITH THE TABLE.
  
 9) P0.1 & P1.1: PROVIDE AN EQUIPMENT SCHEDULE FOR THE
 CIRCULATION PUMP AND VERIFY REQUIRED AUTOMATIC ON/OFF
 CONTROLS WILL BE PROVIDED- SECTION C404.6.1 FBC EC.
  
 10) P1.1 & P1.2: VERIFY THE WATER SERVICE PIPE AND
 WATER DISTRIBUTION PIPES ARE ADEQUATELY SIZED TO
 PROVIDE THE REQUIRED FLOW RATES AND PRESSURES FOR THE
 NEW FIXTURES PER TABLE 604.3 FBC P.
  
 11) P1.1. & P1.2: TEMPERATURE LIMITING DEVICES ARE
 REQUIRED TO PROVIDE TEMPERED WATER TO THE LAVATORIES-
 SECTION 416.5 FBC P. PLEASE INCLUDE THE DEVICES IN THE
 FIXTURE SCHEDULE ON SHEET P0.1- SECTION 607.1.2 FBC P.
  
 12) P1.2: PROVIDE SYMBOLS TO SHOW THE LOCATIONS OF THE
 REQUIRED WATER HAMMER ARRESTORS ON THE WASHING MACHINE
 SUPPLY LINES AND ALL OTHER FIXTURES OR APPLIANCES WITH
 QUICK CLOSING VALVES- SECTION 604.9 FBC P.
  
 13) P1.2: PROVIDE SYMBOLS TO SHOW THE LOCATIONS OF THE
 REQUIRED BACKFLOW PREVENTERS ON WATER LINES CONNECTING
 TO THE COFFEE MACHINE, ICE MACHINE, ICE MAKERS ETC.-
 SECTIONS 608.3, 608.16.1 & 608.16.10 FBC P.
  
 14) P1.2 & P1.3: FIXTURE TRAP AND FIXTURE VENT SIZES
 NOT SHOWN- TABLE 709.1 AND SECTION 906.2 FBC P.
  
 15) P1.1 & P1.3: IT APPEARS THE FLOOR DRAINS IN THE
 MAIN SHOW ROOM WILL BE VENTED VIA A COMBINATION WASTE
 AND VENT SYSTEM PER SECTION 915.1 FBC P, HOWEVER NO
 VENT SIZES ARE SHOWN IN THE ISOMETRIC TO VERIFY
 ADEQUATE SIZING AND DISTANCE AS REQUIRED BY SECTIONS
 915.2.3 THROUGH 915.2.5.
  
 16) P1.1 & P1.3: SHOW THE HUB DRAIN CONNECTIONS INTO
 THE ISOMETRIC DRAWING- SECTION 710.1 FBC P.
  
 17) P1.1 & P1.3: IT APPEARS TWO FD'S LOCATED UPSTREAM
 OF THE DELI DRAIN BRANCH CONNECTION ARE NOT SHOWN IN
 THE ISOMETRIC- SECTION 710.1 FBC P
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  