| Plan Review Notes For Permit 20021256 |
| Permit Number |
20021256 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-03-09 16:11:14 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | | | | 1) SHEET A 0.0 THE CODE INFORMATION SECTION # 6 | | | INDICATES NFPA 101 2018, WHICH IS INCORRECT. | | | | | | THE CURRENT EDITION OF NFPA 101 IS THE 6TH ED, 2015. | | | | | | PLEASE CORRECT AND ENSURE COMPLIANCE. | | | | | | | | | | | | 2) SHEET AC 1.0 - THERE APPEARS TO BE SHELVING IN THE | | | STORAGE COOLER | | | | | | PLEASE PROVIDE SHELF MATERIAL, HEIGHT AND TYPE OF | | | STORAGE DETAILS. | | | | | | | | | 3) SHEET A C 1.0 - THERE DOES NOT APPEAR TO BE AN EXIT | | | SIGN WITHIN THE STORAGE COOLER | | | | | | PLEASE PROVIDE. | | | | | | | | | 4) SHEET AC 1.0 - THE THE STORAGE AREA THERE IS | | | REFERNCE TO TWO RACKS, HOWEVER, THERE IS NO CALL OUT | | | DETAIL FOR WHAT THESE RACKS ARE. | | | | | | PLEASE PROVIDE RACK MATERIAL, HEIGHT AND TYPE OF | | | STORAGE DETAILS. | | | | | | | | | | | | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | | | | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|