Plan Review Notes For Permit 20021256
Permit Number 20021256
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-03-09 16:11:14THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET A 0.0 THE CODE INFORMATION SECTION # 6
 INDICATES NFPA 101 2018, WHICH IS INCORRECT.
  
 THE CURRENT EDITION OF NFPA 101 IS THE 6TH ED, 2015.
  
 PLEASE CORRECT AND ENSURE COMPLIANCE.
  
  
  
 2) SHEET AC 1.0 - THERE APPEARS TO BE SHELVING IN THE
 STORAGE COOLER
  
 PLEASE PROVIDE SHELF MATERIAL, HEIGHT AND TYPE OF
 STORAGE DETAILS.
  
  
 3) SHEET A C 1.0 - THERE DOES NOT APPEAR TO BE AN EXIT
 SIGN WITHIN THE STORAGE COOLER
  
 PLEASE PROVIDE.
  
  
 4) SHEET AC 1.0 - THE THE STORAGE AREA THERE IS
 REFERNCE TO TWO RACKS, HOWEVER, THERE IS NO CALL OUT
 DETAIL FOR WHAT THESE RACKS ARE.
  
 PLEASE PROVIDE RACK MATERIAL, HEIGHT AND TYPE OF
 STORAGE DETAILS.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  