| Plan Review Notes For Permit 20021256 |
| Permit Number |
20021256 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-03-05 13:38:38 | BUILD OUT | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | | | | CORRECTIONS NEEDED - | | | 1) PLEASE SHOW THE EXISTING EXTERIOR EXIT DOORS SIZES | | | TO COMPLY WITH FBC 1010.1.1 | | | 2) PLEASE SHOW THE EXITING SLIDING EXTERIOR EXIT DOORS | | | TO COMPLY WITH FBC 1010.1.4.3 | | | 3) PLEASE PROVIDE WALK IN COOLER WALL AND CEILING | | | DETAILS ( TYPE OF WALL OR CEILING PANEL, ATTACHMENTS TO | | | ASSEMBLE AND ATTACHMENTS TO THE EXISTING STRUCTURE. FBC | | | 1607.14 | | | 4) PLEASE SHOW ATTACHMENT TO FOUNDATION OF HIGH PILE | | | STORAGE RACKS TO COMPLY WITH FBC 2209.1 AND FIRE | | | SPRINKLERS PER FBC 903.2.7.1 |
|