| 2020-03-02 03:33:20 | 1) THE DESCRIPTION OF WORK ON THE APPLICATION STATES |
| | "NEW PLUMBING " AND SPECS FOR A BACKFLOW DEVICE HAVE |
| | BEEN SUBMITTED. THE DESCRIPTION OF WORK ON THE |
| | APPLICATION IS SO VAGUE I CANNOT APPROVE THIS PERMIT. |
| | IS THERE ANY OTHER PLUMBING WORK BEING DONE? PLACE A |
| | CLEAR DESCRIPTION ON THE PERMIT APPLICATION OF THE |
| | ENTIRE SCOPE OF WORK TO BE DONE.WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 2) THE MAKE, MODEL AND SIZE OF THE DEVICE SHALL BE |
| | NOTED IN THE DESCRIPTION OF WORK SECTION ON THE PERMIT |
| | APPLICATION. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 3) ON WHAT TYPE OF SYSTEM IS THE DEVICE BEING INSTALLED |
| | ( DOMESTIC WATER, IRRIGATION)? PLACE THIS INFORMATION |
| | ON THE PERMIT APPLICATION. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 4) IS THIS DEVICE BEING INSTALLED AT THE WATER METER ( |
| | CONTAINMENT) OR IS IT BEING INSTALLED ON A BRANCH OFF |
| | THE DOMESTIC LINE (ISOLATION)? PLACE THIS INFORMATION |
| | ON THE PERMIT APPLICATION. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 5) PIPING FROM THE WATER METER TO THE INLET OF THE |
| | BACKFLOW ASSEMBLY SHALL BE TYPE "K" OR "L" COPPER, |
| | BRASS OR STAINLESS STEEL PER CITY OF WEST PALM BEACH |
| | STANDARD DETAIL DRAWING WS-11. |
| | 6) THE VALUE NOTED ON THE APPLICATION SEEMS LOW. SUBMIT |
| | A DETAILED, QUANTITY ESTIMATE OR BONA FIDE SIGNED |
| | CONTRACT FOR THIS WORK. WPB AMEND. TO FBC SEC. 109.3. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | |