| 2020-03-27 17:11:15 | 03/27/2020 MET WITH MIRIAM. TOLD HER THAT THE SET OF |
| | PLANS SHE SUBMITTED WAS THE FIELD COPY . NO NEED TO |
| | SUBMIT TO US. GAVE THE PLANS BACK TO HER, BUT SHE |
| | RE-SUBMITT THEM AGAIN. |
| | |
| | |
| | SECOND BUILDING REVIEW CHECKLIST. |
| | |
| | 1- OK. |
| | |
| | 2- REVISE ENERGY CALCULATIONS: |
| | (A) PROVIDE CORRECT JURISDICTION NUMBER (604700). |
| | (B)REVISE DOOR INFORMATION PAGE 3 OF 4. DOOR NOA |
| | 17-1212.10 SUBMITTED IS FOR GLAZED DOOR. THIS DOOR |
| | NEEDS TO BE IN WINDOW GLAZING AREA. SEC. R405.5.3.3 |
| | FBC-ENERGY CONSERVATION. |
| | (C) REVISE OVERHANG DEPTH AND SEPARATION OF WINDOW |
| | LOCATED ON THE NORTH SIDE. SEE PLANS AND REVISE AS |
| | REQUIRED. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. ENERGY CALCULATIONS WERE NOT REVISED. |
| | SAME ENERGY CALCULATIONS THAT WERE INITIALLY APPROVED |
| | WITH THE PROVISO THAT THEY WILL BE REVISED WERE |
| | SUBMITTED. NEED TO REVISE THE ENERGY CALCULATIONS |
| | SHOWING THE REQUESTED REVISION. |
| | |
| | 3- DOOR NOA 17-1212.10 DON'T HAVE IMPACT GLAZING. |
| | PROVIDE SHUTTERS PRODUCT APPROVAL (2 COPIES) AND |
| | COMPLETE INSTALLATION SCHEDULE. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |