Plan Review Notes
Plan Review Notes For Permit 20021194
Permit Number 20021194
Review Stop B
Sequence Number 2
Notes
Date Text
2020-03-27 17:11:1503/27/2020 MET WITH MIRIAM. TOLD HER THAT THE SET OF
 PLANS SHE SUBMITTED WAS THE FIELD COPY . NO NEED TO
 SUBMIT TO US. GAVE THE PLANS BACK TO HER, BUT SHE
 RE-SUBMITT THEM AGAIN.
  
  
 SECOND BUILDING REVIEW CHECKLIST.
  
 1- OK.
  
 2- REVISE ENERGY CALCULATIONS:
 (A) PROVIDE CORRECT JURISDICTION NUMBER (604700).
 (B)REVISE DOOR INFORMATION PAGE 3 OF 4. DOOR NOA
 17-1212.10 SUBMITTED IS FOR GLAZED DOOR. THIS DOOR
 NEEDS TO BE IN WINDOW GLAZING AREA. SEC. R405.5.3.3
 FBC-ENERGY CONSERVATION.
 (C) REVISE OVERHANG DEPTH AND SEPARATION OF WINDOW
 LOCATED ON THE NORTH SIDE. SEE PLANS AND REVISE AS
 REQUIRED.
  
 RESPONSE:
 REPEAT COMMENT. ENERGY CALCULATIONS WERE NOT REVISED.
 SAME ENERGY CALCULATIONS THAT WERE INITIALLY APPROVED
 WITH THE PROVISO THAT THEY WILL BE REVISED WERE
 SUBMITTED. NEED TO REVISE THE ENERGY CALCULATIONS
 SHOWING THE REQUESTED REVISION.
  
 3- DOOR NOA 17-1212.10 DON'T HAVE IMPACT GLAZING.
 PROVIDE SHUTTERS PRODUCT APPROVAL (2 COPIES) AND
 COMPLETE INSTALLATION SCHEDULE.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  