2020-03-17 10:21:022017 FBC- PLUMBING PLAN REVIEW
 W. P. B. PERMIT: 20021169
 ADD: 2475 MERCER AVE. SUITE: 105
 CONT: SEARCH CONSTRUCTION, INC.
 TEL: 561-346-8191
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MARCH 017TH/ 2020
 ACTION: DENIED
 1) BOTH SETS OF PLANS IN THE TITLEBLOCK SOMEONE HAS
 USED PEN TO SCRATCH THROUGH AND HAND WRITTEN WPB AS
 PART OF THE ADDRESS.
 61G1-16.004 TITLE BLOCK. ARCHITECT. (3) NAME OR
 IDENTIFICATION OF PROJECT.
  
 2) SHEET A-1 THE BREAKROOM SINK IS SHOWN TO BE
 ACCESSIBLE COUNTER AT 32 INCHES ABOVE FINISH FLOOR. IT
 WOULD APPEAR YOU ARE GOING TO USE A SIDE APPROACH TO
 THE SINK. PLEASE SHOW YOUR CLEAR FLOOR AREA 30X 48
 INCHES FOR A SIDE APPROACH. 2017 FBC-ACCESSIBILITY CODE
 305.5 & FIGURE 305.5(B) PARALLEL APPROACH.
  
 3) SHEET A-1 HANDICAPPED ACCESSIBLE DETAILS:
  
 3A) PLEASE NOTE THE GRAB BAR FOR THE WATER CLOSET IS
 SHOWN TO BE MEASURED/ DIMENSIONED FROM FINISH FLOOR TO
 THE CENTERLINE OF THE GRAB BAR.
 2017 FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION OF
 GRAB BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE, NOT CENTERLINE.
  
 3B) PLEASE NOTE THE TOILET PAPER HOLDER FOR PLACEMENT
 IS SHOWN TO BE CENTERLINE 36 INCHES FROM THE REAR WALL
 LINE. PLEASE SHOW COMPLIANCE WITH TOILET PAPER
 DISPENSERS. 2017 FBC-ACCESS. CODE 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS.
 DISPENSERS SHALL NOT BE OF A TYPE THAT CONTROLS
 DELIVERY OR THAT DOES NOT ALLOW CONTINUOUS PAPER FLOW.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP & CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved