| 2020-03-03 13:11:52 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20021169 |
| | ADD: 2475 MERCER AVE. SUITE: 105 |
| | CONT: SEARCH CONSTRUCTION, INC. |
| | TEL: 561-346-8191 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. MARCH 03/2020 |
| | ACTION: DENIED |
| | 1) BOTH SETS OF PLANS IN THE TITLEBLOCK SOMEONE HAS |
| | USED PEN TO SCRATCH THROUGH AND HAND WRITTEN WPB AS |
| | PART OF THE ADDRESS. |
| | 61G1-16.004 TITLE BLOCK. ARCHITECT. (3) NAME OR |
| | IDENTIFICATION OF PROJECT. |
| | |
| | 2) SHEET A-1 THE BREAKROOM SINK IS SHOWN TO BE |
| | ACCESSIBLE COUNTER AT 32 INCHES ABOVE FINISH FLOOR. IT |
| | WOULD APPEAR YOU ARE GOING TO USE A SIDE APPROACH TO |
| | THE SINK. PLEASE SHOW YOUR CLEAR FLOOR AREA 30X 48 |
| | INCHES FOR A SIDE APPROACH. 2017 FBC-ACCESSIBILITY CODE |
| | 305.5 & FIGURE 305.5(B) PARALLEL APPROACH. |
| | |
| | 3) SHEET A-1 HANDICAPPED ACCESSIBLE DETAILS: |
| | |
| | 3A) PLEASE NOTE THE GRAB BAR FOR THE WATER CLOSET IS |
| | SHOWN TO BE MEASURED/ DIMENSIONED FROM FINISH FLOOR TO |
| | THE CENTERLINE OF THE GRAB BAR. |
| | 2017 FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION OF |
| | GRAB BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL |
| | POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE |
| | THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING |
| | SURFACE, NOT CENTERLINE. |
| | |
| | 3B) PLEASE NOTE THE TOILET PAPER HOLDER FOR PLACEMENT |
| | IS SHOWN TO BE CENTERLINE 36 INCHES FROM THE REAR WALL |
| | LINE. PLEASE SHOW COMPLIANCE WITH TOILET PAPER |
| | DISPENSERS. 2017 FBC-ACCESS. CODE 604.7 DISPENSERS. |
| | TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| | SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT |
| | OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE |
| | DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15 |
| | INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH |
| | FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS. |
| | DISPENSERS SHALL NOT BE OF A TYPE THAT CONTROLS |
| | DELIVERY OR THAT DOES NOT ALLOW CONTINUOUS PAPER FLOW. |
| | |
| | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |