| 2020-03-03 13:57:41 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20021115 |
| | ADD: 1200 S. FLAGLER DR. SUITE: 303 |
| | CONT: CAMBRIDGE CONSTRUCTION LLC |
| | TEL: 561-784-3722 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. MARCH 03/2020 |
| | ACTION: DENIED |
| | |
| | 1) W 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATIVE CODE |
| | 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE |
| | EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H) |
| | ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C) |
| | (BUILDING) REQUIRES THE CONTRACTOR TO BE LICENSED IN |
| | THE TRADE THAT THEY WILL BE CREATING THE PLANS TO BE |
| | SUBMITTED TO THE BUILDING DEPARTMENT. FOR EACH TRADE |
| | THE CONTRACTOR RESPONSIBLE FOR THE PLAN MUST PRINT |
| | THEIR NAME, SIGN THEIR NAME AND LICENSE NUMBER. |
| | |
| | 2) THE SUBMITTED FLOOR PLAN HAS A NOTE TO DROP THE |
| | CEILINGS IN BOTH BEDROOMS TO ACCOMMODATE NEW CEILING |
| | FANS. THE PLANS ARE SILENT AS TO HOW FAR THE CEILINGS |
| | ARE TO BE DROPPED. THE PLANS DO NOT INDICATE THE TYPE |
| | OF ANCHOR TO BE FASTENED INTO THE CONCRETE DECK ABOVE, |
| | DEPTH OF FASTENER INTO THE CONCRETE DECK, IS THE |
| | CONCRETE DECK POST TENSION? |
| | PROVIDE THE TYPE OF FRAMING MEMBER TO BE INSTALLED SIZE |
| | AND SPACING, PLEASE NOT THIS IS A HIGHRISE AND ALL |
| | FRAMING MEMBERS ARE TO BE NON-COMBUSTIBLE. PLEASE |
| | PROVIDE THE JOIST SPACING IN INCHES, THE SPAN, IS THE |
| | MID-POINT UNSUPPORTED OR IS THERE A MID-SPAN SUPPORT. |
| | PLEASE PROVIDE THE TYPE OF CEILING MATERIAL AND |
| | THICKNESS AND ALLOWABLE SPANS? 2017 FBC-B 2508.1/ TABLE |
| | 2508.1 STEEL FRAMING FOR GYPSUM BOARD ASTM C754. |
| | |
| | 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, SFP & CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |