| 2020-03-13 20:02:03 | REVISION BUILDING REVIEW CHECKLIST. | | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | | | 1- SPECIFY THE SIZE AND ORIENTATION OF THE I STUDS TO | | | VERIFY COMPLIANCE WITH THE MAXIMUM HORIZONTAL SPAN FOR | | | I-STUD ASSEMBLIES AS SHOWN ON THE TABLE OF USG ASSEMBLY | | | SUBMITTED ON SHEET A2.1.1. | | | SEC. 107.2.1 CITY AMENDMENTS. | | | | | | 2- CLARIFY WHY THE FIRE RATED PARTITION WAS REVISED AND | | | DOESN'T GO ALL THE WAY UP TO THE BOTTOM OF THE CEILING. | | | SEC. 107.2.1 CITY AMENDMENTS. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|