| 2020-02-27 07:09:27 | 02/27/2020 PLUMBING 1ST REVIEW **DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF |
| | THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH |
| | FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA |
| | STATUTE 471. WPB AMENDMENTS TO THE FBC SEC. 107.1 |
| | GENERAL. |
| | |
| | 2. PLEASE SUBMIT MANUFACTURER'S SPECIFICATION |
| | SHEETS/INSTALLATION MANUAL FOR BBQ AND GAS POOL HEATER |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH 2017 FBC RES. SEC. |
| | G2408.1. |
| | 3. INDICATE ON THE PLAN IF THE GRILL IS LOCATED UNDER A |
| | ROOF PER THE WPB AMENDMENTS TO FBC SEC. 107.2.1. |
| | |
| | 4. IF THE GAS GRILL IS UNDER A COVER ROOF OR PATIO AND |
| | GAS GRILL IS LABELED FOR OUTSIDE USE, THEN PLEASE |
| | PROVIDE MANUFACTURES RECOMMENDATION FOR A VENTILATION |
| | HOOD PER THE 2017 FBC RES. SEC. G2408.1. |
| | |
| | 5. SUBMIT TWO COPIES OF THE SIZING TABLE USED IN THE |
| | DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS |
| | OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR |
| | ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS |
| | SYSTEM PER THE 2017 FBC RES. SEC. G2413.3. |
| | |
| | 6. IF NOT DONE SO ALREADY, PLEASE SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS |
| | INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE |
| | APPROVED FOR OUTDOOR INSTALLATION PER THE 2017 FBC RES. |
| | SEC. G2421.1. |
| | |
| | 7. PLEASE SHOW ALL UNIONS IN FRONT OF REGULATOR 1' OF |
| | EITHER SIDE PER THE 2017 FBC RES. SEC G2421.2. |
| | |
| | 8. PLEASE SHOW AND LABEL THE SHUTOFF VALVE, DRIP LEG |
| | AND REGULATOR ON GAS ISOMERIC PER THE 2017 FBC RES. |
| | SEC. G2401.1.3. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |